User guide
78
Help Windows
Window text Help Text
Regulation Mode (Normal Default) Pumping regulation mode, normal or inverse.
See page 64.
Start Value Start value, allows pressure to drop in system
PSI or Selected Units before unit starts. (Disabled is default) See page 64.
Config. 2nd Required Value Configuration of a second value from another
Off (Default) sensor. See page 64.
Relay Configuration Relay configuration. See page 64.
Run Motor (Default)
Submenu Submenu offset: to enter push “ “ key
Offset for at least two seconds.
Offset Input Selection of offset input, if required.
Off (Default) See page 49.
Level 1 Start level for offset 1.
XX.X % See page 50.
Level 2 Start level for offset 2.
XX.X% See page 50.
Intensity 1 Intensity of offset 1.
XX.X% See page 51.
Intensity 2 Intensity of offset 2.
XX.X% See page 51.
Submenu Submenu seq. control; to enter push “ “ key
Seq. Control for at least two seconds. See pages 52 and 53.
Pressure Incr. Pressure increment at switching of additional pumps
4 PSI in multicontroller mode. See pages 52 and 53.
Pressure Dec. Pressure decrement for consecutive pumps.
4 PSI See pages 52 and 53.
Enable Seq. Ctl. Frequency limit enable sequence control. Starts
58 Hz (Default) second pump in multicontroller. See page 55, step 9.
Switch Interval Time interval pump sequence change. Allows
12h (Default) multiple pumps to lead/lag in system, based on
switch interval time. See page 55, step 10.
*
*