User guide
80
Help Windows
Window text Help Text
Test Run Man. Start test run with up and down arrows
(Inc + Dec) simultaneously.
Test Frequency Test frequency. Frequency at when motor
30.0 Hz will run in test mode.
Submenu Submenu: errors; to enter push “ “ key
Errors for at least two seconds.
Conveyor Limit Value at which pump system shall be deactivated,
due to lack of NPSH or system pressure.
Delay Seconds Enter a time the pump is allowed to run after a
Disabled (Default) suction line sensor has activated, or conveyor
limit has been reached.
Error Reset Automatic error reset measured in seconds. The
On AV II will restart 5 times. If error is still present,
the AV II will stay off on faults.
Clear Errors Clear error history, enter 0726
0000 and press the “ ” key.
Operating Hours Total AQUAVAR controller operating time
xxxxh (reset counters: press the up and down arrows).
Disp. Contrast Display contrast, 0-100% contrast.
100%, 50% Default
Set Password Modify password enables the user to set a new
0000 password.
Lock Function On > keypad locked: off > changes allowed.
Off
Submenu Submenu load default parameters to enter
Default Values push select at least 1 second.
Default USA/Europe Reset to default parameters for US or European
Press up and down arrows (if needed). settings.
Save ??? Press Inc + Dec to save entered values
Inc + dec
*
*