User Manual

Intertek Testing & Certification Limited, Cleeve Road, Leatherhead, Surrey, KT22 7SB
Tel: + 44 (0)1372 370900, Fax: +44 (0)1372 370977, E-mail: cpd.uk@intertek.com
0359-CPR-00406
Issue 2
www.intertek.com
Registered No 3272281 Academy Place, 1-9 Brook Street, Brentwood, Essex,
CM14 5NQ, United Kingdom
This Certificate is for the exclusive use of Intertek's client and is provided pursuant to the agreemen
t between Intertek and its Client. Intertek's responsibility
and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other tha
n to the Client in accordance with the
agreement, for any loss, expense or damage occasioned by the use of this Certificate. Only the Client is authorized to permit copying or distribution of thi
s
Certificate and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the
tested material, product or
service must first be approved in writing by Intertek.
Page 3 of
3
Certificate of Constancy of Performance
0359-CPR-00406
Appendix to Certificate of Constancy of Performance 0359-CPR-00406 (continued)
Table of performance for EN54-24:2008
Harmonised technical specification
Essential characteristics Performance
Clauses Notes
Performance under fire condition. Pass 4.2, 5.2, 5.3, 5.4, 5.5 a
Operational reliability Pass 4.3, 4.4, 4.5, 5.6, 5.18 b
Durability of operational reliability:
temperature resistance
Pass 5.7, 5.8, 5.9 b
Durability of operational reliability:
humidity resistance
Pass 5.10, 5.11, 5.12 b
Durability of operational reliability:
corrosion resistance
Pass 5.13
Durability of operational reliability:
impact and vibration resistance
Pass 5.14, 5.15, 5.16, 5.17 c
Notes:
a. The products covered by this standard are assumed to enter the alarm condition, in an event of fire, before the fire
becomes so large as to affect their functioning. There is therefore no requirement to function when exposed to direct
attack from fire.
b. For Clauses 5.7, 5.9, 5.10 and 5.18, Type B conditioning was applied.
c. Model VXS8-VA and Model VXS8-VAW exceed 4.75kg in weight; an assessment to Clause 5.14 was therefore not
performed on these models.