Specifications
18 of 46 9000-0447
(+)
4
5
(-)
(-)
1
(-)
3
(+)
2
(+)
(-)
AOM
(+)
8
6
7
9
FCI P/N 119-90015
SLC
TERMINALS
-
+
POWER SUPPLY
TERMINALS
7
AMM-2
54 5
90
6
8
3
2
1
9
8
7
6
4
0
1
2
3
YEL
END-OF-LINE RESISTOR
P/N 151-00014
SUPERVISION RELAY
VIO
MONITOR MODULE
CONNECTED TO SLC
NOTICE:
SOLENOID
SEE ADDENDUM, P/N 9000-0427 FOR
A LIST OF UL LISTED FCI APPROVED
RELEASING DEVICES
MAX. 20 FT. 18AWG (MIN.)
IN RIGID CONDUIT
SUPERVISED
NON POWER-LIMITED
P/N 151-00014
47K 1/2W
P/N 4310-0510
1N4004
USE ONLY THE LISTED AND APPROVED METHODS AND DEVICES REFERENCED IN THIS MANUAL TO ACTUATE A
FIRE EXTINGUISHING SYSTEM. REFER TO THE INSTALLATION MANUAL FOR THE PROPER USE OF THE SYSTEM
IN A PARTICULAR APPLICATION. EXTINGUISHING AGENTS THAT SUPPRESS FIRES BY OXYGEN DILUTION SUCH
AS CARBON DIOXIDE AND VARIOUS INERT GASES SHALL BE PROVIDED WITH LISTED, APPROVED,
MECHANICALLY OPERATED TIME DELAYS AND STOP VALVES TO CONTROL THE DISCHARGE TO A PROTECTED
AREA.
WIRING FROM THE POWER SUPPLY TO THE AOM MODULE NOT TO EXCEED 2 OHMS. POWER FOR ACTUATING
RELEASE SOLENOIDS MUST BE OBTAINED FROM THE NON-RESETTABLE POWER TERMINALS OF THE SPSU-V,
BSM-2, THE FCI FC-72 PS-6 OR APS-6, OR ANY 24 VDC REGULATED POWER SUPPLY LISTED FOR FIRE
SIGNALING SYSTEMS PER UL864 AND/OR 1481 AND FACTORY MUTUAL SYSTEM APPROVED.
CONNECTIONS TO THE SOLENOID WIRE LEADS AND SUPERVISORY RESISTOR/DIODE COMBINATION MUST BE
VIA LISTED TERMINAL BLOCKS IN A STANDARD LISTED ELECTRICAL BOX CLOSE-NIPPLED TO THE SOLENOID.
7
54
90
6
8
3
2
1
5
9
8
7
6
4
0
1
2
3
TENS
DIGIT
ONES
DIGIT
MODULE ADDRESS SWITCHES
ASSIGN EACH MODULE A UNIQUE SLC ADDRESS
Figure 3a Typical Releasing Circuit Wiring