Rapid Shutdown Solutions

CODE REQUIREMENTS - NEC 2014 RAPID SHUTDOWN (Article 690.12)
PV system circuits installed in or on buildings shall include a rapid shutdown function that controls specic conductors in
accordance with NEC 2014, Article 690.12 (1) through (5). These requirements include:
1. Rooftop PV installations
2. Rapid shutdown equipment placement:
a. 10 feet from array (equipment outside building) or
b. 5 feet from array (equipment inside building)
3. Shutdown to 30V & 240VA in 10 seconds
4. Correct stickers/signage
5. All PV equipment listed and identied
RAPID SHUTDOWN SOLUTIONS
COMPLYING WITH NEC 2014
www.solectria.com | inverters@solectria.com | 978.683.9700
RESIDENTIAL INSTALLATIONS
SOLUTION: Yaskawa - Solectria Solar Residential PVI 3800-7600TL inverters and Rapid Shutdown Combiner Box
REQUIREMENTS: Installer must wire 5VDC control signal to inverter from Rapid Shutdown Combiner Box.
METHODS:
Methods to meet NEC 2014 Rapid Shutdown with minimal
rooftop electronics (small added cost)
ARRAY
Two Story Home
INVERTER
RAPID SHUTDOWN
RELAY BOX
Methods to meet NEC 2014 Rapid Shutdown without
any rooftop electronics (NO added cost)
ARRAY
Two Story Home
INVERTER
INDOORS
<5’ CONDUCTORS
Methods to meet NEC 2014 Rapid Shutdown without
any rooftop electronics (NO added cost)
ARRAY
One Story Ranch or Bungalow
INVERTER
OUTDOORS
< 10’ CONDUCTORS
EAVES AT
ONE STORY
(2) Two Story Home (3) One Story Ranch or Bungalow
(1) Two Story Home

Summary of content (2 pages)