Access Level <1> 
No.  Parameter Name 
Setting 
Range 
Units  Default  Description 
During 
Run 
V/f 
V/f 
with PG 
OLV  CLV 
MEMOBUS 
Address 
F5-01  Terminal M1-M2 Output Function    0  During RUN    A  A  A  A  399H 
F5-02  Terminal M3-M4 Output Function    1  Zero Speed    A  A  A  A  39AH 
F5-03  Terminal P1-PC Output Function    2  Speed Agree 1    A  A  A  A  39BH 
F5-04  Terminal P2-PC Output Function    4  Frequency Detection 1    A  A  A  A  39CH 
F5-05 
Terminal P3-PC Output Function 
n 
 6 Drive Ready   A A A A 30DH 
F5-06  Terminal P4-PC Output Function    37  During Frequency Output    A  A  A  A  39EH 
F5-07  Terminal P5-PC Output Function    F  Terminal Not Used    A  A  A  A  39FH 
F5-08  Terminal P6-PC Output Function 
0 to 
192 
<9> 
  F  Termianl Not Used    A  A  A  A  3A0H 
Digital Output Card 
F5-09  DO-A3 Output Mode Selection  0 to 2    0 
0: Terminal functions according to default 
settings 
1: Binary code output 
2: Terminal functions selected by parameters 
F5-01 through F5-08. 
 A A A A 3A1H 
F6-01 
Communications Error Operation 
Selection 
0 to 3    1 
0: Ramp to stop 
1: Coast to stop 
2: Emergency stop 
3: Continue running   
 A A A A 3A2H 
F6-02 
Selection of External Fault from 
Communication Option Board 
0,1  0 
0: Always detected 
1: Detection during run only 
 A A A A 3A3H 
F6-03 
Stopping Method for External 
Fault from Communication Option 
Board 
0 to 3    1 
0: Ramp to stop 
1: Coast to stop 
2: Emergency stop 
3: Continue running 
 A A A A 3A4H 
F6-04 
Trace Sampling from 
Communications Option Board 
0.0 to 5.0  0.1 s  2.0 
Delay time for error detection if a bus error 
occurs 
 A A A A 3A5H 
F6-06 
Torque Reference/Torque Limit 
Selection from Communications 
Option 
0,1  0 
0: Disabled 
1: Enabled 
 - - - A 3A7H 
F6-07 
Multi-Step Speed Reference 
selection with NetRef/ComRef 
0,1  0 
0: Multi-step reference disabled (same as F7) 
1: Multi-step reference enabled (same as V7) 
 A A A A 3A8H 
F6-08  Reset Communication Parameters  0,1    0 
0: Communication-related parameters are not 
reset when the drive is initialized using A1-03. 
1: Reset all communication-related 
parameters   when the drive is initialized 
using A1-03. 
 A A A A 36AH 
Communication Option Card Settings 
F6-10 
Throug
h 
F6-
Refer to the technical manual included with the option card 
H1-01  Terminal S1 Function Selection      40  Forward RUN Command    A  A  A  A  438H 
H1-02  Terminal S2 Function Selection      41  Reverse RUN Command    A  A  A  A  439H 
H1-03  Terminal S3 Function Selection      24  External Fault N.O Always Detected    A  A  A  A  400H 
H1-04  Terminal S4 Function Selection      14 Fault Reset    A A A A 401H 
H1-05  Terminal S5 Function Selection      0  Brake Release Check    A  A  A  A  402H 
H1-06  Terminal S6 Function Selection      3  Multi-Step Speed Reference 1    A  A  A  A  403H 
H1-07  Terminal S7 Function Selection      4  Multi-Step Speed Reference 2    A  A  A  A  404H 
Digital Inputs 
H1-08  Terminal S8 Function Selection   
0 to 9F 
<9> 
9  Baseblock Command N.C.    A  A  A  A  405H 
H2-01 
Terminal M1-M2 Function 
Selection 
21  Brake Release Command    A  A  A  A  40BH 
H2-02 
Terminal M3-M4 Function 
Selection 
0 During RUN    A A A A 40CH 
H2-03 
Terminal M5-M6 Function 
Selection 
00 to 
192 
<9> 
  2  Speed Agree 1    A  A  A  A  40DH 
Digital Outputs 
H2-06  Watt Hour Output Unit Selection  0 to 4    0 
0: 0.1 kW units 
1: 1 kW units 
2: 10 kW units 
3: 100 kW units 
4: 1000 kW units 
 A A A A 437H 
<1>  Access Levels  A: Advanced Programming Menu  Q: Quick Setting Menu  -: N/A in this Control Mode 
<9>  For more information on available functions for input and output terminals refer to section 5.4 of this document. For a detailed description of each 
standard function refer to section 5.7 of the A1000 standard drive technical manual (SIEP C710616 27). 