Specifications

YASKAWA Inverter Drive A1000 – Crane Software Application Manual
17
Access Level <1>
No. Parameter Name
Setting
Range
Units Default Description
During
Run
V/f
V/f
with PG
OLV CLV
MEMOBUS
Address
H3-01
Terminal A1 Signal Level
Selection
0,1 0
0: 0 Vdc to +10 Vdc
1: -10 Vdc to +10 Vdc
A A A A 410H
H3-02 Terminal A1 Function Selection
0 to 31
<9>
0 Frequency Bias A A A A 411H
H3-03 Terminal A1 Input Gain
-999.9
to
999.9
0.1% 100.0
Sets the input value when 10 Vdc is input at
A1
A A A A 411H
H3-04 Terminal A1 Input Bias
-999.9
to
999.9
0.1% 0.0 Sets the input value when 0 Vdc is input at A1 A A A A 412H
H3-05
Terminal A3 Signal Level
Selection
0,1 0
0: 0 Vdc to +10 Vdc
1: -10 Vdc to +10 Vdc
A A A A 413H
H3-06 Terminal A3 Function Selection
0 to 31
<9>
2 Aux Frequency Reference 1 (Multi-Step 2) A A A A 414H
H3-07 Terminal A3 Input Gain
-999.9
to
999.9
0.1% 100.0
Sets the input value when 10 Vdc is input at
A3
A A A A 415H
H3-08 Terminal A3 Input Bias
-999.9
to
999.9
0.1% 0.0 Sets the input value when 0 Vdc is input at A3 A A A A 416H
H3-09
Terminal A2 Signal Level
Selection
0 to 2 2
0: 0 Vdc to +10 Vdc
1: -10 Vdc to +10 Vdc
2: 4 to 20 mA
3: 4 to 20 mA
A A A A 417H
H3-10 Terminal A2 Function Selection
0 to 31
<9>
0 Frequency Bias A A A A 418H
H3-11 Terminal A2 Input Gain
-999.9
to
999.9
0.1% 100.0
Sets the input value when 10 Vdc (20 mA) is
input at terminal A2
A A A A 419H
H3-12 Terminal A2 Input Bias
-999.9
to
999.9
0.1% 0.0
Sets the input value when 0 Vdc (4 mA) is
input at terminal A2
A A A A 41AH
H3-13 Analog Input Filter Time Constant
0.00 to
2.00
0.01 s 0.03
Primary delay filter time for all analog input
terminals. Used to filter noisy signals
A A A A 41BH
H3-14
Analog Input Terminal Enable
Selection
1 to 7 7
Determines which of the analog input
terminals will be enabled when H1-

= C.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
A A A A 41CH
H3-16 Terminal A1 Tuning Offset
-500
to 500
0
Adds an offset when the analog input signal at
terminal A1 is 0 Vdc.
A A A A 2F0H
H3-17 Terminal A2 Tuning Offset
-500
to 500
0
Adds an offset when the analog input signal at
terminal A2 is 0 Vdc (4 mA).
A A A A 2F1H
Analog Inputs
H3-18 Terminal A3 Tuning Offset
-500
to 500
0
Adds an offset when the analog input signal at
terminal A3 is 0 Vdc.
A A A A 2F2H
H4-01 Terminal FM Monitor Selection
000 to
999
102
Sets the monitor to be output to terminal FM.
For example to output U1-02 enter “102”
A A A A 41DH
H4-02 Terminal FM Gain
-999.9
to
999.9
0.1% 100.0
Sets the signal level at terminal FM that
equals 100% of the selected monitor value.
Q,A Q,A Q,A Q,A 41EH
H4-03 Terminal FM Bias
-999.9
to
999.9
0.1% 0.0
Sets the signal level at terminal FM that
equals 0% of the selected monitor value.
A A A A 41FH
H4-04 Terminal AM Monitor
000 to
999
103
Sets the monitor to be output to terminal AM.
For example to output U1-02 enter “102”
A A A A 420H
H4-05 Terminal AM Gain
-999.9
to
999.9
0.1% 50.0
Sets the signal level at terminal AM that
equals 100% of the selected monitor value.
Q,A Q,A Q,A Q,A 421H
H4-06 Terminal AM Bias
-999.9
to
999.9
0.1% 0.0
Sets the signal level at terminal AM that
equals 0% of the selected monitor value.
A A A A 422H
H4-07
Terminal FM Signal Level
Selection
0,1 0
0: 0 Vdc to +10 Vdc
1: -10 Vdc to +10 Vdc
A A A A 423H
Analog Outputs
H4-08
Terminal AM Signal Level
Selection
0,1 0
0: 0 Vdc to +10 Vdc
1: -10 Vdc to +10 Vdc
A A A A 424H
<1> Access Levels A: Advanced Programming Menu Q: Quick Setting Menu -: N/A in this Control Mode
<9> For more information on available functions for input and output terminals refer to section 5.4 of this document. For a detailed description of each
standard function refer to section 5.7 of the A1000 standard drive technical manual (SIEP C710616 27).