Specifications

YASKAWA Inverter Drive A1000 – Crane Software Application Manual
18
Access Level <1>
No. Parameter Name
Setting
Range
Units Default Description
During
Run
V/f
V/f
with
PG
OLV CLV
MEMOBU
S
Addres
s
H5-01 Node Address
0 to FF
(Hex)
1F MEMOBUS / Modbus Address. A A A A 425H
H5-02 Communication Speed Selection 0 to 8 3
0: 1200 bps 5: 38400 bps
1: 2400 bps 6: 57600 bps
2: 4800 bps 7: 76800 bps
3: 9600 bps 8: 115200 bps
4: 19200 bps
A A A A 426H
H5-03 Communication Parity Selection 0 to 2 0
0: Parity disabled
1: Odd parity
2: Even Parity
A A A A 427H
H5-04
Stopping Method After
Communication Error (CE)
0 to 3 3
0: Ramp to stop
1: Coast to stop
2: Emergency stop
3: Continue running
A A A A 428H
H5-05
Communication Error Detection
Selection
0,1 1
0: Disabled
1: Enabled. If communication is lost for more
than H5-09 seconds, a CE fault will occur
A A A A 429H
H5-06 Drive Transmit Wait Time 5 to 65 1 ms 5 Wait time between receiving and sending data A A A A 42AH
H5-07 RTS Control Selection 0,1 1
0: Disabled. RTS is always on
1: Enabled. RTS turns on only when sending
A A A A 42BH
H5-09
Communication Error Detection
Time
0.0 to
10.0
0.1 s 2.0
Time required to detect a Communication
Error
A A A A 435H
H5-10
Unit Selection for
MEMOBUS/Modbus Register
0025H
0,1 0
0: 0.1 V units
1: 1 V units
A A A A 436H
H5-11
Communications ENTER Function
Selection
0,1 0
0: Drive requires an Enter command before
accepting any changes to parameter settings
1: Parameter changes are activated
immediately without the Enter command
A A A A 43CH
MEMOBUS Comm.
H5-12 Run Command Method Selection 0,1 0
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
A A A A 43DH
H6-01
Pulse Train Input Function
Selection
0 0 0: Frequency reference A A A A 42CH
H6-02 Pulse Train Input Scaling
1000
to
32000
1 Hz 1440
Sets the input signal frequency that is equal to
100% of the function set in H6-01
A A A A 42DH
H6-03 Pulse Train Input Gain
0.0 to
1000.0
0.1% 100.0
Sets the level of the function selected in H6-01
when a frequency of H6-02 is input
A A A A 42EH
H6-04 Pulse Train Input Bias
-100.0
to
100.0
0.1% 0.0
Sets the level of the function set in H6-01
when 0 Hz is input
A A A A 42FH
H6-05 Pulse Train Input Filter Time
0.00 to
2.00
0.01 s 0.10 Pulse train input filter time constant A A A A 430H
H6-06 Pulse Train Monitor Selection
000 to
809
102
Used to select the monitor that the pulse train
output should use
A A A A 431H
H6-07 Pulse Train Monitor Scaling
0 to
32000
1 Hz 1440
Sets the pulse train output frequency when the
monitor value is 100%
A A A A 432H
Pulse Train I/O
H6-08
Pulse Train Input Minimum
Frequency
0.1 to
1000
0.1 Hz 0.5
Minimum input frequency for pulse train
detection
A A A A 43FH
L1-01
Motor Protection Function
Selection
0 to 6 1
0: Disabled
1: General purpose motor (standard fan
cooled)
2: Drive dedicated motor with a speed range
of 1:10
3: Vector motor with a speed range of 1:100
6: Standard motor (50 Hz)
Q,A Q,A Q,A Q,A 480H
L1-02 Motor Protection Operation Time
0.1 to
5.0
0.1
min
1.0 Motor thermal overload protection (oL1) time A A A A 481H
L1-03
Motor Overheat Alarm Operation
Selection (PTC input)
0 to 3 3
0: Ramp to stop
1: Coast to stop
2: Emergency stop
3: Alarm only (oH3 will flash)
A A A A 482H
L1-04
Motor Overheat Fault Operation
Selection (PTC input)
0 to 2 1
0: Ramp to stop
1: Coast to stop
2: Emergency stop
A A A A 483H
L1-05
Motor Temperature Input Filter
Time Constant
0.00 to
10.00
0.01 s 0.20 Filter time constant for PTC analog input A A A A 484H
Motor Protection
L1-13
Continuous Electrothermal
Operation Selection
0,1 1
0: Enabled
1: Disabled
A A A A 46DH
<1> Access Levels A: Advanced Programming Menu Q: Quick Setting Menu -: N/A in this Control Mode