Specifications
YASKAWA Inverter Drive A1000 – Crane Software Application Manual 
19 
Access Level <1> 
No.  Parameter Name 
Setting 
Range 
Units  Default  Description 
During 
Run 
V/f 
V/f 
with PG 
OLV  CLV 
MEMOBUS 
Address 
P
ower
Loss
L2-05 
DC Bus Undervoltage Detection 
Level 
150 to 
210 
<7> 
1 Vdc 
190 
<7> 
DC Bus voltage level at which an undervoltage 
fault is triggered. 
 A A A A 489H 
L3-01 
Stall Prevention Selection during 
Acceleration 
0 to 2    1 
0: Disabled 
1: General Purpose 
2: Intelligent 
 A A A - 48FH 
L3-02 
Stall Prevention Level during 
Acceleration 
0 to 
200 
1% 150 
Stall prevention level as a % of drive rated 
current 
 A A A - 490H 
L3-03 
Stall Prevention Limit during 
Acceleration 
0 to 
100 
1% 50 
Stall prevention lower limit during acceleration 
as a % of drive rated current. 
 A A A - 491H 
L3-04 
Stall Prevention Selection during 
Deceleration 
0 to 6 
<10> 
0 
0: Disabled 
1: General Purpose 
2: Intelligent 
3: Stall Prevention Function with braking 
resistor 
4: Overexcitation Deceleration 1 
5: Overxcitation Deceleration 2 
 Q,A Q,A Q,A Q,A 492H 
L3-05 
Stall Prevention Selection 
during Run 
0 to 2    1 
0: Disabled 
1: Enabled (decel time C1-02) 
2: Enabled (decel time C1-04) 
 A A - - 493H 
L3-06 
Stall Prevention Level during 
Run 
30 to   
200 
1% 160 
Stall prevention level as a % of drive rated 
current 
 A A - - 494H 
L3-11 
Overvoltage Suppression 
Function Selection 
0,1  0 
0: Disabled   
1: Enabled   
 A A A A 4C7H 
L3-17 
DC Bus Voltage for Overvoltage 
Suppression and Stall Prevention 
150 to 
400 
<7> 
1 Vdc 
375 
<7> 
DC Bus voltage level at which overvoltage 
suppression and stall prevention are triggered 
during deceleration. 
 A A A A 462H 
L3-20  DC Bus Voltage Adjustment Gain 
0.00 to 
5.00 
 0.30 
Proportional gain for KEB, Overvoltage 
Suppression and Stall Prevention 
 A A A A 465H 
L3-21  Accel/Decel Rate Calculation Gain 
0.00 to 
200.00 
 1.00 
Proportional gain used to calculate decel rate 
when KEB, Overvoltage Suppression and Stall 
Prevention are triggered during deceleration 
 A A A A 466H 
L3-23 
Automatic Reduction Selection for 
Stall Prevention during Run   
0,1  0 
0: Sets the Stall Prevention level set in L3-06 
that is used throughout the entire frequency 
range. 
1: Automatic Stall Prevention level reduction in 
the constant output range. 
 A A - - 4FDH 
L3-24 
Motor Acceleration Time for 
Inertia Calculations 
0.001 
to 
10.000 
0.001 
s 
0.178 
Time needed to accelerate the uncoupled 
motor at rated torque from zero de maximum 
frequency 
 A A A A 46EH 
L3-25  Load Inertia Ratio 
1.0 to 
1000.0 
  1.0  Ratio between motor and machine inertia    A  A  A  A  46FH 
L3-26  Additional DC Bus Capacitors 
0 to   
65000 
1μf 0 
Equivalent capacitance value when additional 
capacitors have been added to the DC Bus. 
 A A A A 455H 
Stall Prevention 
L3-27  Stall Prevention Detection Time 
0 to   
5000 
1 ms  50 
Time that current must exceed the stall 
prevention level before stall prevention is 
triggered. 
 A A - - 456H 
L4-01  Speed Agreement Detection Level   
0.0 to 
400.0 
0.1 Hz  0.0 
Frequency detection level for digital output 
functions H2-02 through H2-05 
 A A A A 499H 
L4-02  Speed Agreement Detection Width 
0.0 to 
20.0 
0.1 Hz  2.0 
Hysteresis or margin for speed agreement in 
L4-01 
 A A A A 49AH 
L4-03 
Speed Agreement Detection 
Level (+/-) 
-400.0 
to 
400.0 
0.1 Hz  0.0 
Frequency detection level for digital output 
functions H2-13 through H2-16 
 A A A A 49BH 
L4-04 
Speeed Agreement Detection 
Width (+/-) 
0.0 to   
20.0 
0.1 Hz  2.0 
Hysteresis or margin for speed agreement in 
L4-04 
 A A A A 49CH 
L4-05 
Frequency Reference Loss 
Detection Selection 
0,1  0 
0: Enabled 
1: Disabled 
 A A A A 49DH 
L4-06 
Frequency Reference at 
Reference Loss 
0.0 to 
100.0 
0.1% 80.0 
Percentage of last frequency reference that 
the drive should run at when the reference is 
lost 
 A A A A 4C2H 
Speed Detection 
L4-07 
Speed Agreement Detection 
Selection 
0,1  0 
0: Disabled during baseblock 
1: Always enabled 
 A A A A 470H 
<1>  Access Levels  A: Advanced Programming Menu  Q: Quick Setting Menu  -: N/A in this Control Mode 
<7>  Values shown are for 200 VAC class drives. For 400 VAC class drives these values are doubled. 
<10> Set to 3 (Stall Prevention w/ Braking Resistor) when in Closed Loop Vector (CLV) control 










