Specifications

YASKAWA Inverter Drive A1000 – Crane Software Application Manual
25
Access Level <1>
No. Parameter Name
Setting
Range
Units Default Description
During
Run
V/f
V/f
with PG
OLV CLV
MEMOBUS
Address
S5-01
Overload Detection Operation
Selection 1
0 to 6 - 0
0: Disabled
1: Detection only during Speed Agree,
acceleration prohibited (continue running). Alarm
only
2: Detection during run, acceleration prohibited
(continue running). Alarm only
3: Detection only during Speed Agree.
Decelerate to stop at Fast Stop time (C1-09).
Alarm only
4: Detection during run. Decelerate to stop at
Fast Stop time (C1-09). Alarm only
5: Detection only during Speed Agree. Interrupt
output current. Fault
6: Detection during run. Interrupt output current.
Fault
A A A A 6B0H
S5-02 Overload Detection Level 1
0 to
300
1% 150 Sets Motor Overload 1 detection threshold <14> A A A A 6B1H
S5-03 Overload Detection Time 1
0.0 to
10.0
0.1 s 0.1
Time during which Overload Detection level 1
must be surpassed to trigger Overload Detection
output
A A A A 6B2H
S5-04
Overload Detection Operation
Selection 2
0 to 6 - 0
0: Disabled
1: Detection only during Speed Agree,
acceleration prohibited (continue running). Alarm
only.
2: Detection during run, acceleration prohibited
(continue running). Alarm only.
3: Detection only during Speed Agree.
Decelerate to stop at Fast Stop time (C1-09).
Alarm only.
4: Detection during run. Decelerate to stop at
Fast Stop time (C1-09). Alarm only.
5: Detection only during Speed Agree. Interrupt
output current. Fault
6: Detection during run. Interrupt output current.
Fault
A A A A 6B3H
S5-05 Overload Detection Torque 2
0 to
300
1% 150 Sets Motor Overload 2 detection threshold <14> A A A A 6B4H
Overload Detection
S5-06 Overload Detection Time 2
0.0 to
10.0
0.1 s 0.1
Time during which Overload Detection level 2
must be surpassed to trigger Overload Detection
output
A A A A 6B5H
S6-01
Overtorque Detection Operation
Selection 1
0 to 6 0
0: Disabled
1: Detection only during Speed Agree,
acceleration prohibited (continue running). Alarm
only
2: Detection during run, acceleration prohibited
(continue running). Alarm only
3: Detection only during Speed Agree. Interrupt
output current. Fault
4: Detection during run. Interrupt output current.
Fault
5: Detection only during Speed Agree (continue
running), but maintain multi-function digital
output until stopped. Alarm only
6: Detection duuing run, but maintain
Multi-Function Digital output until stopped. Alarm
only
A A A A 6B6H
S6-02 Overtorque Detection Level 1
0 to
300
1% 150 Sets motor Overtorque Detection Level 1 <14> A A A A 6B7H
S6-03 Overtorque Detection Time 1
0.0 to
10.0
0.1 s 0.1
Time during which Overtorque Detection level 1
must be surpassed to trigger Overload Detection
output
A A A A 6B8H
S6-04
Overtorque Detection Operation
Selection 2
0 to 6 0
0: Disabled
1: Detection only during Speed Agree,
acceleration prohibited (continue running). Alarm
only
2: Detection during run, acceleration prohibited
(continue running). Alarm only
3: Detection only during Speed Agree. Interrupt
output current. Fault
4: Detection during run. Interrupt output current.
Fault
5: Detection only during Speed Agree (continue
running), but maintain multi-function digital
output until stopped. Alarm only
6: Detection duuing run, but maintain
multi-function digital output until stopped. Alarm
only
A A A A 6B9H
S6-05 Overtorque Detection Level 2
0 to
300
1% 150 Sets motor Overtorque Detection Level 2 <14> A A A A 6BAH
Overtorque Detection
S6-06 Overtorque Detection Time 2
0.0 to
10.0
0.1 s 0.1
Time during which Overtorque Detection level 2
must be surpassed to trigger Overload Detection
output
A A A A 6BBH
<1> Access Levels A: Advanced Programming Menu Q: Quick Setting Menu -: N/A in this Control Mode
<14> In V/f Control, set as a % of motor rated current. In Vector Control, set as a % of motor rated torque.