 Normal / Heavy Duty Selection (C6-01)
The drive supports two ratings, Normal Duty and Heavy Duty. Both have different output current ratings (refer to the 
catalog or Technical Manual). Set the Duty mode in accordance with the application.
 Auto-Tuning (T1-)
Auto-Tuning automatically sets up the motor data relevant drive parameters. Three different modes are supported
Open Loop Vector Control 
for PM
<1>
A1-02 = 5
Derated torque-load applications employing permanent magnet motors (SPM, IPM) and energy 
savings.
Advanced Open Loop 
Vector Control for PM
<1>
A1-02 = 6 This control mode can be used to operate an IPM motor for constant torque applications.
Closed Loop Vector 
Control for PM <1>
A1-02 = 7
• This mode can be used for high precision control of a PM motor in constant torque or variable 
torque applications. 
• A speed feedback signal is required.
<1> For explanations of these control modes, refer to the Technical Manual
Mode Heavy Duty Rating (HD) Normal Duty Rating (ND)
C6-01 01
Application
Applications with a constant torque like extruders, 
conveyors and cranes. High overload capability might 
be needed.
Applications where the torque increases with the speed 
like fans or pumps. High overload tolerance is normally 
not needed.
Overload capability (OL2) 150% of drive rated current for 60 s 120% of drive rated current for 60 s
L3-02 Stall Prevention during 
Acceleration
150% 120%
L3-06 Stall Prevention during 
Run
150% 120%
Default carrier frequency 2 kHz 2 kHz Swing PWM
Type Setting Application Conditions and Benefits
Control Mode (A1-02)
V/f (0)
V/f w/PG 
(1)
OLV (2) CLV (3)
Rotational Auto-
Tuning
T1-01 = 0
• Motor can be decoupled from the load and rotate freely 
while Auto-Tuning is performed.
• Motor and load can not be decoupled but the motor load 
is below 30%.
• Rotational Auto-Tuning gives the most accurate results, 
and is therefore highly recommended if possible.
N/A N/A YES YES
Stationary Auto-
Tuning 1
T1-01 = 1
• Motor and load can not be decoupled and the load is 
higher than 30%.
• A motor test report listing motor data is not available. 
• Automatically calculates motor parameters needed for 
vector control. 
N/A N/A YES YES
Stationary Auto-
Tuning 2
T1-01 = 4
• Motor and load can not be decoupled and the load is 
higher than 30%.
• A motor test report is available. Once the no-load current 
and the rated slip have been entered, the drive calculates 
and sets all other motor-related parameters.
N/A N/A YES YES
Stationary Auto-
Tuning for Line-to-
Line Resistance
T1-01 = 2
• The drive is used in V/f Control and other Auto-Tuning 
selections not possible.
• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and 
motor has been replaced with a cable over 50 m long. 
Assumes Auto-Tuning has already been performed.
• Should not be used for any vector control modes unless 
the motor cable has changed.
YES YES YES YES
Control Mode Parameter Main Applications