Specifications
8 Safe Disable Input Function
32  YASKAWA ELECTRIC TOEP C710616 27A YASKAWA AC Drive - A1000 Quick Start Guide
Safe Disable Status Monitor
With the Safe Disable monitor output (terminals DM+ and DM-), the drive provides a safety status feedback signal. This 
signal should be read by the device that controls the Safe Disable inputs (PLC or a safety relay) in order to prohibit 
leaving the “Safe Torque Off” status in case the safety circuit malfunctions. Refer to the instruction manual of the safety 
device for details on this function.
Digital Operator Display
When both Safe Disable inputs are open, “Hbb” will flash in the digital operator display.
Should only one of the Safe Disable channels be on while the other is off, “HbbF” will flash in the display to indicate that 
there is a problem in the safety circuit or in the drive. This display should not appear under normal conditions if the Safe 
Disable circuit is utilized properly. Refer to General Fault and Alarms on page 26 to resolve possible errors.
OFF ON ON
Safely disabled, “Safe 
Torque Off”
HbbF (flashes)
ON ON ON
Baseblock, ready for 
operation
Normal display
Safe Disable Input Status Safe Disable Status 
Monitor,
DM+ - DM-
Drive Output Status Digital Operator Display
Input 1, H1-HC Input 2, H2-HC