Specifications

3 Electrical Installation
YASKAWA Europe TOEP C710616 88A - AC Drive A1000 IP23/54 Floor Standing - Quick Start Guide EN 17
Motor side cable connections
The way the motor cable is connected to the drive depends on the optional components installed on the output side. Refer
to the table below for terminal labelling, screw sizes and torque values.
Braking unit connection
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within the specification listed below.
Output
Model A14
0208 0250 0296 0362 0414 0515 0675
Direct Connection to Drive
Terminal Screw Size M10 M12
Torque (Nm) 20 32
Identification U/T1, V/T2, W/T3
Output Choke
Terminal Screw Size M10 M12
Torque (Nm) 20 32
Identification U/T1, V/T2, W/T3
Braking Unit Circuit
Cable Size
(mm²)
Screw Size Torque (Nm) Identification
CDBR-4090D
Control 0.75 - 1.5 M4 1.5 1, 2, 3, 4, 5, 6
Braking Resistor 4 - 6 M5 2.5 +0, -0’
CDBR-4220D
Control 0.75 - 1.5 M4 1.5 1, 2, 3, 4, 5, 6
Braking Resistor 10 - 16 M6 4.9
,
Wire Type Wire size (mm
2
) Ferrule Length (mm)
Solid 0.2 to 1.5 -
Flexible 0.2 to 1.0 -
Flexible with ferrule (recommended) 0.25 to 0.5 8
0
0