Specifications
3 Electrical Installation
YASKAWA Europe TOEP C710616 88A - AC Drive A1000 IP23/54 Floor Standing - Quick Start Guide EN 21
NOTICE: The terminals HC, H1, H2 are used for the Safe Disable function. Do not remove the wire link between HC, H1, or H2 unless
the Safe Disable function is used. Refer to Safe Disable Input Function on page 40 when using this function.
NOTICE: The wiring length to the terminals HC, H1 and H2 should not exceed 30 m.
Monitor Output
MP
Pulse train output (Output frequency) 32 kHz (max)
FM
Analog monitor output 1 (Output frequency)
-10 to +10 V DC, 0 to +10 V DC, or 4 to 20 mA
Use jumper S5 on the control terminal board to select between
voltage or current output at terminals AM and FM. Set
parameters H4-07 and H4-08 accordingly when changing the
jumper setting.
AM
Analog monitor output 2 (Output current)
AC
Monitor common 0 V
DM+
Safety monitor output
Outputs status of Safe Disable function. Closed when both
Safe Disable channels are closed. Up to +48 V DC 50 mA
DM-
Safety monitor output common
Type No. Terminal Name (Function) Function (Signal Level) Default Setting