MP Series Ethernet (Extension) Driver
GP-Pro EX Device/PLC Connection Manual
12
Settings of External Device
Communication setting of communication module 218IF-02 by ladder software (MPE720).
Please refer to the manual of external device for more detail.
Ladder Software Setting
1 Start ladder software, make an order folder and a PLC folder in a root folder.
2 Click the right button of the PLC which select logon in the displayed menu.
3 Double-click the [Definition folder]-[Module constitution] of the PLC folder, and display [Engineering Manager].
4 Select the rack classification and communication module, the pull-down menu in [Controller] of [Engineerring
Manager].
Set the number corresponding to the slot number that a communication module uses.
Select the communication module, setting contents are displayed to [Module details] of [Enginnering Manager].
5 Double-click the number part at No. in [Module details].
Double-click the slot number connecting the ethernet unit.
6 Save setting content and finish [Engineering Manager].
7 DIP switch "INIT" of a communication module is ON and spend a power supply.
8 Forward communication setting to a communication module.
9 Logon the PLC at online and write in the data which transferred at flash memory.
10 Power supply of PLC is OFF and DIP switch of the INIT is OFF, after spend the power supply of PLC.
Notes
Check with a network administrator about IP address. Do not set the duplicate IP address.
Logon after confirming that a check does not begin [online] of a displayed menu.
Refer to User's Manual of the PLC about a method of logon.
Setup Items Setup Description
Transmission parameter This Station IP address PLC IP address
Please make the connection parameter a blank.
When the connection parameter is set, it cannot communicate.