Specifications

37
Constant Descriptions
Use Four (4) Types of Accel/Decel Time
Acceleration time 1 to 4 C1-01, C1-03, C1-05, C1-07
Deceleration time 1 to 4 C1-02, C1-04, C1-06, C1-08
Accel/decel time setting unit C1-10
Multi-function input H1-01 to 05
* When stopping method is deceleration to stop (b1-03=0).
Output
Frequency
Acceleration Time 1
Deceleration Time 1(C1-02)
Deceleration Time 2
(C1-04)
Deceleration Time 1
(C1-02)
Time
ONON OFF
ON
Acceleration Time 2(C1-03)
(C1-01)
Forward (Reverse)
Run Command
Accel/Decel Time Switch
(one of terminals S3 to S12)
Set
07
or
1A
(accel/decel time switch 1 or 2) in multi-function input
(H1-01 to 10), to allow selection of 4 sets of accel/decel times by the
ON/OFF of the accel/decel time switch (one of terminals S3 to S12).
Accel/decel Time Selection 2
Multi-function Input
Setting = 1A
Accel Time Decel Time
Accel/decel Time Selection 1
Multi-function Input
Setting = 07
Constant
No.
C1-01
C1-02
C1-03
C1-04
C1-05
C1-06
C1-07
C1-08
Accel time 1
Decel time 1
Accel time 2
Decel time 2
Accel time 3
Decel time 3
Accel time 4
Decel time 4
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
0.1 s
(1s for 1000s or more)
0.0 to
6000.0 s
0.0 to
6000.0 s
0.0 to
6000.0 s
0.0 to
6000.0 s
0.0 to
6000.0 s
0.0 to
6000.0 s
0.0 to
6000.0 s
0.0 to
6000.0 s
0.1 s
(1s for 1000s or more)
0.1 s
(1s for 1000s or more)
0.1 s
(1s for 1000s or more)
0.1 s
(1s for 1000s or more)
0.1 s
(1s for 1000s or more)
0.1 s
(1s for 1000s or more)
0.1 s
(1s for 1000s or more)
Name Unit
Setting
Range
Factory
Setting
Open or not set
Open or not set
Closed
Closed
C1-01
C1-03
C1-05
C1-07
C1-02
C1-04
C1-06
C1-08
Open or not set
Closed
Open or not set
Closed
* C1-10 = 0 : Units of 0.01 sec. (Max. 600.00 seconds)
C1-10 = 1 : Units of 0.1 sec. (Max. 6000.00 seconds)
Soft Start
S-curve characteristic time C2-01 to 04
Accel/decel by S-curve pattern can be accomplished to
prevent shock at start, or stop of the machine.
Setting the S-curve characteristic time, the acceleration or deceleration
time will be longer by 1/2 of the S-curve characteristic time at start or end.
C2-01
C2-02
C2-03
C2-04
Constant
No.
S-curve characteristic time
at acceleration start
S-curve characteristic time
at acceleration end
S-curve characteristic time
at deceleration start
S-curve characteristic time
at deceleration end
0.20 s
0.20 s
0.20 s
0.00 s
0.00 to
  2.50 s
0.00 to
  2.50 s
0.00 to
  2.50 s
0.00 to
  2.50 s
Function
Setting
Range
Factory
Setting
Note: S-curve characteristic time is the time required for the 0 accel/decel rate to reach
the formal accel/decel rate determined by the preset accel/decel time.
Frequency Reference
Output Frequency
Output Frequency
Time
S-curve Characteristic Time (Tsc)
Forward Run Command
Reverse Run Command
Characteristics in
Acceleration
Deceleration
DecelerationAcceleration
Minimum Output Frequency
Min. Output Frequency
DC Braking Time at Stop
Output Frequency
b2-04
C2-04
C2-03
C2-03
C2-02
C2-02
C2-01
C2-01
C2-04 E1-09
E1-09
Time Chart when Switching Forward Run and Reverse Run at
Deceleration to Stop (V/f control mode example)