Frequency Detection
Multi-function terminal function selection
H2-01 to 03
Frequency detection level L4-01,L4-03
Frequency detection width L4-02,L4-04
Various frequencies can be detected by setting the
following values in terminal M1-M2, P1 and P2 function
selection (H2-01, 02 and 03).
As shown above, select the detection with or without sign in
the Varispeed G7.
The following is the frequency (speed) agree timing chart. The
figure shows the case of forward rotation; the direction for
reverse rotation without sign is the same. When detection with
sign is selected, detection signal against the specified direction
of rotation is detected according to the direction of rotation.
Setting
Value
01
02
03
04
05
13
14
15
16
Zero-speed
Fref/Fout agree 1
Fref/Set agree 1
Frequency detection 1
(Less than preset value)
Frequency detection 2
(More than preset value)
Fref/Fout agree 2
Fref/Set agree 2
Frequency detection 3
(Less than preset value for the
specified direction of rotation)
Frequency detection 4
(More than preset value for the
specified direction of rotation)
―
Frequency reference
Frequency reference
L4-01
without
sign
L4-03
with sign
―
L4-02
L4-04
Description
Frequency (Speed)
Agree Detection
Level Setting
Constant No.
Frequency (Speed)
Agree Detection
Width Setting
Constant No.
Constant Descriptions
OFFON
L4-02
L4-02
L4-01
L4-01
Output frequency
or motor speed
Freq. Detection 1
(Multi-function output setting = 4)
OFF ON
L4-02
L4-02
L4-01
L4-01
Output frequency
or motor speed
Freq. Detection 2
(Multi-function output setting = 5)
OFF ON
L4-04
L4-04
Frequency
reference
Output frequency
or motor speed
Fref/Fout Agree 2
(Multi-function output setting = 13)
OFF ON
L4-04
L4-03
Output frequency
or motor speed
Fref/Set Agree 2
(Multi-function output setting = 14)
OFFON
L4-04
L4-03
Output frequency
or motor speed
Freq. Detection 3
(Multi-function output setting = 15)
OFF ON
L4-04
L4-03
Output frequency
or motor speed
Freq. Detection 4
(Multi-function output setting = 16)
(3)Setting Value=04:Frequency (FOUT) Detection 1
(4)Setting Value=05:Frequency (FOUT) Detection 2
(5)Setting Value=13:Fref/Fout Agree 2
(6)Setting Value=14:Fref/Set Agree 2
(7)Setting Value=15:Frequency (FOUT) Detection 3
(8)Setting Value=16:Frequency (FOUT) Detection 4
OFF ON
L4-02
L4-02
Frequency
reference
Output frequency
or motor speed
Fref/Fout Agree 1
(Multi-function output setting = 2)
Output frequency
or motor speed
OFF ON
L4-02
L4-01
L4-01
L4-02
Fref/Set Agree 1
(Multi-function output setting = 3)
(1)Setting Value=02:Fref/Fout Agree 1
(2)Setting Value=03:Fref/Set Agree 1