Specifications

44
Use Frequency Meter or Ammeter
Monitor selection (terminal FM) H4-01,H4-04
Analog output signal level selection H4-07,H4-08
Select whether output frequency or output current is to be
output to analog monitor output terminals FM-AC or AM-AC.
Multi-function Analog Monitor 2
−10 to +10 V 2 mA
*1
Output Current at Factory
Setting 0 to +10 V
Output Frequency at Factory
Setting 0 to +10 V
Multi-function Analog Monitor 1
−10 to +10 V 2 mA
*2
*1 −10 to +10 V output can be made
by setting H4-08.
*2 −10 to +10 V output can be made by
setting H4-07.
AM
FM
E(G)
AC
FM
AM
Constant No.
Name Description
H4-01
H4-04
H4-07
H4-08
Monitor selection
(terminal FM)
Set the number of the monitor item
to be output from terminal FM or
AM. (Number in the part
== of
U1-
==.) 4, 10 to 14, 25, 28, 34,
39 to 42 cannot be set. Do not use
17, 23, 29 to 31 and 35.
Set the signal level of terminal FM
or AM.
0 : 0 to +10 V output
1 : 0 to ±10 V output
Monitor selection
(terminal AM)
Signal level selection
(terminal FM)
Signal level selection
(terminal AM)
Reduce Motor Noise or Leakage Current
Carrier frequency C6-02
If the wiring between the inverter and the motor is
excessively long, the inverter output current will be
increased because of the increased leakage current of
harmonics from the cable, which may affect the peripheral
devices.
Refer to the following table to adjust the inverter output
transistor switching frequency (carrier frequency).
Reducing such carrier frequency is effective for reduction
of radio noise.
* Factory setting: C6-02 = 6 (15 kHz: 200 V class 18.5 kW
or below)
Wiring Distance between
Inverter and Motor
Carrier Frequency
C6-02 Value
50 m or less
15 kHz or less
1 to 6
100 m or less
10 kHz or less
1 to 4
More than 100 m
5 kHz or less
1 to 2
C6-02
Setting Value
Carrier Frequency
(kHz)
Metallic Noise
from Motor
Noise and
Leakage Current
2.0
15.0
1
6
Large
Small
Less
More
* 2kHz or more frequency recommended