Specifications
45
Calibrate Indications of Frequency Meter
or Ammeter
Analog Monitor Gain H4-02,H4-05
Analog Monitor Bias H4-03,H4-06
Used when analog output terminals FM-AC and AM-AC
output voltage with gain and bias.
For gain, set how many times of 10V the monitor item 100 %
output is to be made. Set the bias in the units of % assuming
that the amount to move the output characteristics upward
and downward in parallel is to be 10 V/100 %.
For frequency meter that displays 0 to 60 Hz at 0 to 3 V
10 V ×(H4-02 = 0.3 )= 3 V
This is the voltage when the
output frequency is 100 %.
Note: Set 1.00 when using a 10 V full-scale meter.
Bias can be set in the range from −10 to +10 %.
H4-05
Frequency Meter/Ammeter
(3 V 1 mA full-scale)
AM
FM
AM
FM
AC
H4-02
10 V
3 V
5 V
0
100 %
Analog Output Voltage
Output Frequency
(Inverter Output Current)
Factory Setting
H4-02=1.0,H4-03=0
Factory Setting
H4-05=0.5,H4-06=0
Example of H4-02 = 0.3
H4-05 = 0.3
( )
Gain×10 V
10 V
0 V
100 % 0 %
Monitor Item
Analog Output Voltage
Bias× ―― V
100
10
Use Pulse Monitor
Pulse train monitor selection H6-06
Pulse train monitor scaling H6-07
External Power Supply (V)
Sink Current (mA)
12 VAC±10 %,15 VDC±10 %
Up to 16 mA
Sink Current
External Power Supply
MP
Inverter
AC
Load
Impedance
Output Voltage (Insulation Type)
VRL(V)
Load Impedance (kΩ)
+5 V or more
+8 V or more
+10 V or more
1.5 kΩ or more
3.5 kΩ or more
10 kΩ or more
VRL
MP
Inverter
AC
Load
Impedance
Used as sink input
Used as source output
H6-06 Setting Value
Output Item
1
2
5
20
24
36
Frequency reference (U1-01)
Output frequency (U1-02)
Motor speed (U1-05)
Output frequency after soft-start (U1-20)
PID feedback (U1-24)
PID input (U1-36)
When the value of an output item is 100 %, set H6-07 to the
number of pulses to be output in the units of Hz.
To use the pulse monitor, connect the peripheral devices according
to the following load conditions.
If any of the following load conditions is not met, sufficient
characteristics may not be obtained or the devices may be damaged.
Outputs the monitor items [U1-== (status monitor)] of the
digital operator from pulse monitor terminals MP-SC.
Set H6-06 to the numerical value in
== of U1-== (status
monitor). (Only the following 6 items can be output.)
Constant Descriptions