Specifications

58
Fans and Blowers
(Contributes to Energy-saving and Improved Performance)
Power
Supply
Frequency
Reference
Dust
Collection
Device
Damper
Blower
Motor
Exhaust
M
Controller
Manual
4-20 mA
0-10 V
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
MC3 MC2
MC1
Varispeed G7
200 VAC
rs
MC3
Interlock
SA
MX
MX
MX
SA
SA
SA
SA
MC1MC2
MC2
RUNX
MC1
RUN
STOP
Commercial
Inverter
Possible to change
commercial/inverter
without stopping motor.
Motor
IM
MC2MC3
RUNX
Digital
Operator
MC1
Varispeed G7
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
R
S
T
S1
S5
M1
PC
P1
M2
SC
Running
FWD/Stop
A1 and A2 Switching
Signal during
Frequency Missing
Power
Supply
A1
AC
A2
4-20 mA
0
V
0-10 V
User
,
s Requirements
Speed search function b3-01=1
Energy-saving control
Energy-saving mode selection b8-01=1
Coast to stop
Stopping method selection
 b1-03=1
Continue operation
even if failure occurs
in frequency reference
Operation when frequency
reference is missing
        
Reference loss signal  H2-02=C
Operate using control
circuit terminals
Frequency reference
switching between
0 to 10V and 4 to 20mA
Operation method
selection
Terminal A2 signal level selection
H3-08=2
Terminal A2 function selection
H3-09=2
Terminal A1 and A2 switching
(A2 when terminal S5 is ON)
Function and Parameter Settings
Note: In this case, be sure to select coast to stop for inverter
stopping method.
b1-01,02=1
L4-05=1
Application Example
Dust
Collection
System Blower,
Fan for Boilers
Fan for Cooling
Towers
User
,
s Requirements
Applicable Varispeed G7 Function
Function and Parameter Settings
Switch commercial power supply
and inverter drive without stopping
the motor.
Torque limit L7-01=0 to 300 %
Momentary power loss protection
L2-01=0 to 2
Energy-saving mode selection
b8-01=1
Speed search selection b3-01=1
Monitor display U1-08
Frequency reference lower limit
d2-02=0 to 110 %
Jump frequency
d3-01 to 03=0 to 400 Hz
Jump frequency width
d3-04=0 to 20.0 Hz
Fault retry count L5-01=0 to 10 times
Operating signal selection
L4-05=0 to 1
Frequency reference is missing
H2-01 to 03=C
High-efficiency operation with light load
Apply the torque limit function.
Turn the monitor to the output power indication.
Use the fault retry function.
Select the momentary power loss
reset and restart mode.
Select the automatic continuous operation
mode when frequency reference is missing.
Use the preset frequency band
prohibition function (frequency jump
control). Up to 3 frequencies prohibited.
Use the frequency reference lower limit.
Inverter start from coasting stop
status without stopping the motor.
Continue operation even when momentary
power loss not longer than 2 seconds occur.
Continue operation even if a failure occures in
higher-order frequency reference equipment.
min
-
1
lower limit for lubricating
the gear bearing.
Avoid mechanical resonance.
Wants to prevent machine stop
page caused by inverter tripping.
Save energy since the load is not
heavy at low-speed operation.
Avoid overload tripping.
Monitor output power.
The resonance point will be passed,
and continuous operation is
eliminated at this point.
(         )
Use the speed search operation with
speed calculation.
Example of the Use of Inverter with Air Scrubber
Commercial/Inverter Selector Circuit