Specifications

63
Protective Functions
Operation Errors
An operation error will occur if there is an invalid setting or a contradiction between two constant settings. The inverter will not
start until the constants have been set correctly. (The alarm output and fault contact outputs will not operate wither.)
Error
The inverter capacity setting doesn
,
t match the unit. (Contact your YASKAWA representative.)
The constant setting is out of the valid setting range.
Display Meaning
The same setting has been selected for two or more multi-function inputs (H1-01 to 05) or UP or
DOWN command was selected independently, etc.
An option card is not connected when the option card was selected as the frequency reference
source by setting b1-01 to 3.
A PG speed control card is not connected when V/f control with PG was selected by setting
A1-02 to 1.
The same setting has been selected for the analog input selection and the PID function selection.
A setting not required in the control mode has been selected.
PID sleep function is valid (b5-01 0 and b5-15 0) and stop method has been set to 2 or 3.
Constants E1-04, E1-06, E1-07, and E1-09 do not satisfy the conditions.
Constant setting error occurred.
A verification error occurred when writing EEPROM.
Incorrect Inverter Capacity
Setting (OPE01)
Constant Setting Range
Error (OPE02)
Multi-function Input
Selection Error (OPE03)
Multi-function Analog
Input Selection
Error (OPE07)
Constant Selection
Error (OPE08)
PID Control Selection
Error (OPE09)
V/f Data Setting
Error (OPE10)
Constant Setting
Error (OPE11)
EEPROM Write
Error (ERR)
Option Card Reference
Selection Error (OPE05)
Control Mode Selection
Error (OPE06)
OPE01
kVA Selection
OPE02
Limit
OPE03
Terminal
OPE05
Sequence Select
OPE06
PG Opt Missing
OPE07
Analog Selection
OPE08
OPE09
OPE10
V/f Ptrn Setting
OPE11
Carr Freq/On-Delay
ERR
EEPROM R/W Err