Specifications
88
Frequency Meter/Ammeter
*
Frequency Setting Potentiometer
Code No. RH000739
Output Voltmeter
Frequency Setting
Knob
Scale Plate
(Code No. NPJT41561-1)
Frequency Meter Adjusting Potentiometer
Code No. RH000850
Potentiometer
2-M4 Terminal Screws
4-M3 MTG Bolts
Note: For scale of ammeter, contact your YASKAWA representative.
* DCF-6A is 3 V, 1 mA, 3 kΩ. For Varispeed G7 multi-function analog monitor output, set
frequency meter adjusting potentiometer or constant H4-02, -05 (analog monitor output
gain) within the range of 0 to 3 V (initial setting is 0 to 10 V).
Mass:0.3 kg
Mass:20 g
Panel Drilling Plan
in mm
Resistance
2 kΩ
20 kΩ
ETX 3270
ETX 3120
Code No.
4-4 Dia.
Mass:0.2 kg
Panel Drilling Plan
in mm
in mm
Shaft 6 Dia.
2.8
±0.2
Dia.
Dia.
Mass:0.3 kg
Panel Drilling Plan
in mm
in mm
2-M4 Terminal Screws
4-5 Dia.
3.6 Dia.
9.5 Dia.
4-M4 MTG Bolts
85 Dia.
(Code No. VM000481)
(
Output Voltmeter: Code No. VM000502
Transformer for Instrument: Code No. PT000084
)
Scale
75 Hz full-scale: Code No. FM000065
60/120 Hz full-scale: Code No. FM000085
・
・
Adjusts motor frequency through use of frequency setting knob located over the potentiometer.
Corrects frequency meter reading.
Used to adjust potentiometer
frequency setting.
Potential Transformer(Model UPN-B)
Model
600 V Transformer for Instrument
UPN-B 440 V/110 V (400/100 V)
Code No.
100-011-486
Note:
For use with a standard voltage regulator.
A standard voltage regulator may not match the drive
output voltage. Select a regulator specifi cally designed
for the drive output (100-011-486), or a voltmeter that
does not use a transformer and offers direct read out.
Mass: 2.2 kg
Insulation cap
Red: Drive input
Blue: Drive output
Mtg. hole
× 4 (M6)
102±2
31
90
86±2
56±1
Nameplate
101±2
76±2
1.6
Ground
terminal
Terminal block
with cover
(M3 screw)
U V
u v
E
approx. 85
Dimensions in mm