Specifications

89
Isolator (Insulation Type DC Transmission Converter)
Performance
Allowance
Temperature
Influence
Aux. Power
Supply Influence
Load Resistance
Influence
Output Ripple
±0.25 % of output span
(Ambient temp.: 23 ℃)
With ±0.25 % of output span
(The value at ±10 ℃ of ambient temp.)
With ±0.1 % of output span
(The value at ±10 % of aux. power supply.)
With ±0.05 % of output span
(In the range of load resistance)
With ±0.5 % P-P of output span
Response
Time
Withstand
Voltage
Insulation
Resistance
0.5 sec. or less (Time to settle to
±1 % of final steady value)
2000 VAC for one min.
(between each terminal of input,
output, power supply, and enclosure)
20 MΩ and above (by 500 VDC megger).
(between each terminal of input,
output, power supply, and enclosure)
Terminal
1
2
3
4
5
6
7
8
Description
Output +
Output −
Input +
Input −
Grounding
Model Input Signal
Output Signal Power Supply
Code No.
DGP2-4-4
DGP2-4-8
DGP2-8-4
DGP2-3-4
DGP3-4-4
DGP3-4-8
DGP3-8-4
DGP3-3-4
0 to 10 V
0 to 10 V
4 to 20 mA
0 to 5 V
0 to 10 V
0 to 10 V
4 to 20 mA
0 to 5 V
0 to 10 V
4 to 20 mA
0 to 10 V
0 to 10 V
0 to 10 V
4 to 20 mA
0 to 10 V
0 to 10 V
100 VAC
100 VAC
100 VAC
100 VAC
200 VAC
200 VAC
200 VAC
200 VAC
CON 000019.25
CON 000019.26
CON 000019.35
CON 000019.15
CON 000020.25
CON 000020.26
CON 000020.35
CON 000020.15
Input
Power Supply
Load
Power
supply
Wiring Connections
Cable Length
4 to 20 mA:Within 100 m
0 to 10 V :Within 50 m
Mass
Isolator:350 g
Socket 060 g
Dimensions in mm
Product Line
Model DGP
Series
Socket View of socket mounting
Potentiometer
,
s adjuster position varies according to the model.
Adjuster
Terminal
Screws
M3.5
2-4.5 Dia.
Holes
3-phase
Power
Supply
R
S
T
MCCB
Back up
Capacitor Unit
N B1/P
E
Motor
IM
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
B2
G
1
F
J
90
300
280
96
50
4-M6:MTG Screws
When this unit is not used, the inverter
,
s power loss ride-thru ability is 0.1 to 1 second.
Recovery Unit for Momentary Power Loss
(Applicable to models of 0.4 to 7.5 kW (200 V/400 V Class))
Use this unit for 7.5 kW or less to extend the inverter
,
s power loss ride-thru ability to 2 seconds.
200 to 230 V Model P0010
380 to 460 V Model P0020
Connection with Inverter Dimensions in mm
Mass:2 kg
Options, Peripheral Devices