User`s manual

30
Command Code
Reading Writing
Name Data/Unit Description
C Terminal P1 output Terminal P1 output status
D Terminal P2 output Terminal P2 output status
E Reserved
110h
(Cont’d)
Inverter status
(Cont’d)
bit
F Reserved
111h — Reserved
112h — Torque monitor
*2
-300.0% to +300.0% Sets the current motor torque.
113h — Reserved
114h Operation frequency set
value
0.0Hz to 400.0Hz When the PLC does not have the
frequency reference right set to the
inverter, the value is determined
by the inverter setting.
115h Output frequency 0.0Hz to 400.0Hz Current output frequency
116h Output current 0.1A Current output current
117h INV terminal A1 analog
input
0.1% —
118h Main circuit DC voltage 0.1V Sets the value of the main circuit
DC voltage.
119h Error Alarm 1 Refer to the following table.
11Ah Error Alarm 2 Refer to the following table.
11Bh Error Alarm 3 Refer to the following table.
11Ch INV terminal A3 analog
input
0 Terminal S1 input
1 Terminal S2 input
2 Terminal S3 input
3 Terminal S4 input
4 Terminal S5 input
5 Terminal S6 input
6 Terminal S7 input
7 Terminal S8 input
8 Terminal S9 input
*1
9 Terminal S10 input
*1
A Terminal S11 input
*1
B Terminal S12 input
*1
11Dh INV sequence input bit
C to F Not used
The input status of terminals S1 to
S11 (bits 0 to B) is in HEX data.
11Eh INV terminal A1 analog
input
-1540 to 1540 / -11V to +11V
11Fh PG counter 2 1
*1 Applicable only for G7-series Inverters.
*2 Enabled when A1-02 (control mode selection) is set to "3" for flux vector control, "2" for
open-loop control or "3" for flux vector control.