Specifications

User Parameter Tables
5-97
* 1. The settings will be 0.05 (Flux vector)/2.00 (Open-loop vector) for drives of 55kW or larger.
* 2. The settings shown are for 208-240Vac Drives. The values will double for 380-480Vac Drives.
* 3. Settings vary as shown in the following tables depending on the Drive capacity and E1-03.
* 4. The setting range is 0 to 66.0 for open-loop vector control 2.
E1-07
E3-05
Mid Output Frequency A
0.0 to 400.0 0.1Hz
3.0
*3
3.0
*3
3.0 0.0 0.0
Mid Frequency A
E1-08
E3-06
Mid Output Voltage A
*2
0.0 to 255.0
(0.0 to 510.0)
0.1 V
15.0
*3
15.0
*3
11.0 0.0 0.0
Mid Voltage A
E1-09
E3-07
Minimum Output Frequency
0.0 to 400.0 0.1Hz
1.5
*3
1.5
*3
0.5 0.0 0.3
Min Frequency
E1-10
E3-08
Minimum Output Voltage
*2
0.0 to 255.0
(0.0 to 510.0)
0.1 V
9.0
*3
9.0
*3
2.0 0.0 1.0
Min Voltage
F1-09
Overspeed Detection Delay Time
0.0 to 2.0 0.1 s - 1.0 - 0.0 0.0
PG Overspd Time
n5-01
Feed Forward Control Selection
0, 1 1 - - - 0 1
Feedfoward Sel
Parameter
Number
Name
Setting Range Unit
Factory Setting
Display
V/f
Control
V/f with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2