Specifications

Monitor Parameters
6-79
Monitor Parameters
This section explains the analog monitor and pulse monitor parameters.
" Using the Analog Monitor Parameters
This section explains the analog monitor parameters.
!Related Parameters
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
H4-01
Terminal FM
Monitor
Selection
Selects the monitor output (U1-xx)
function for terminals FM and FC.
Refer to "U1-xx" monitors for
available settings.
Unavailable settings:
4, 10, 11, 12, 13, 14, 25, 28, 29, 30,
31, 34, 35, 39, 40, 41, 42, 47, 49, 50
1 to 48 2 No A A A A A
Terminal FM
Sel
H4-02
Terminal FM
Gain Setting
Sets terminal FM output level when
selected monitor is at 100%.*
1
0.0
to
1000.0
100% Yes Q Q Q Q Q
Terminal FM
Gain
H4-03
Terminal FM
Bias Setting
Sets terminal FM output level when
selected monitor is at 0%.*
1
-110.0
to
110.0
0.0% Yes A A A A A
Terminal FM
Bias
H4-04
Terminal AM
Monitor
Selection
Selects which monitor will be the
output on terminals AM and FC.
Same function choices as H4-01.
1 to 48 3 No A A A A A
Terminal AM
Sel
H4-05
Terminal AM
Gain Setting
Sets terminal AM output voltage (in
percent of 10Vdc) when selected
monitor is at 100% output.*
1
0.0
to
1000.0
50.0%YesQQQQQ
Terminal AM
Gain
H4-06
Terminal AM
Bias Setting
Sets terminal AM output voltage (in
percent of 10Vdc) when selected
monitor is at 0% output.*
1
-110.0
to
110.0
0.0% Yes A A A A A
Terminal AM
Bias
H4-07
Terminal FM
Signal Level
Selection
Selects the signal level of terminal
FM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*
2
*Set the analog output jumper
CN15 in the proper position.
0 to 2 0 NoAAAAA
AO Level
Select1