User`s manual

5-5
5
d1-01
Frequency
reference 1
Sets the master frequency reference.
0 to
150.00
*2
0.00 HzYesQQQQ280H
Reference 1
d1-02
Frequency
reference 2
Sets the frequency reference when
multi-step speed command 1 is ON for a
multi-function input.
0.00 HzYesQQQQ281H
Reference 2
d1-03
Frequency
reference 3
Sets the frequency reference when
multi-step speed command 2 is ON for a
multi-function input.
0.00 HzYesQQQQ282H
Reference 3
d1-04
Frequency
reference 4
Sets the frequency reference when
multi-step speed command 1 and 2 are
ON for a multi-function input.
0.00 HzYesQQQQ283H
Reference 4
d1-17
Jog fre-
quency ref-
erence
Sets the frequency reference when
multi-function inputs „Jog Frequency
Command“, „FJOG command“, or
„RJOG command“is ON.
6.00 HzYesQQQQ292H
Jog Refer-
ence
E1-01
Input volt-
age setting
Sets the inverter input voltage. This set
value will be the basis for the protection
functions.
155 to
255
*3
230 V
*3
NoQQQQ300H
Input
Voltage
E1-03
V/f pattern
selection
0 to E: Select from 15 preset patterns.
F: Custom user-set pattern (Appli-
cable for the setting of E1-04 to
E1-10).
0 to F F No Q Q No Q 302H
V/f
Selection
E1-04
Max. output
frequency
(FMAX)
40.0 to
150.0
*2
50.0 Hz NoQQQQ303H
Max
Frequency
E1-05
Max. voltage
(VMAX)
0.0 to
255.0
*3
200.0 V
*3
NoQQQQ304H
Max Voltage
E1-06
Base fre-
quency (FA)
0.0 to
150.0
*2
50.0 Hz
*4
NoQQQQ305H
Base Fre-
quency
E1-09
Min. output
frequency
(FMIN)
0.0 to
150.0
*2
0.5 Hz
*4
NoQQQQ308H
Min Fre-
quency
E1-13
Base voltage
(VBASE)
Sets the output voltage at the base fre-
quency (E1-06).
0.0 to
255.0
*3
0.0 V
*5
NoAAQQ30CH
Base Volt-
age
E2-01
Motor rated
current
Sets the motor rated current in Amps.
This set value becomes the base value
for motor protection and torque limit. It
is an input data for autotuning.
0.32 to
6.40
*5
1.90 A
*6
NoQQQQ30EH
Mtr Rated
Power
E2-04
Number of
motor poles
Sets the number of motor poles. It is an
input data for autotuning.
2 to 48 4 No No Q No Q 311H
Number of
Poles
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display