User`s manual

5-46
5
H3-09 Settings
Setting
Value
Function Contents (100%)
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Closed
Loop
Vector
0 Frequency bias Maximum output frequency Yes Yes Yes Yes 6-27
1 Frequency gain
Frequency reference (voltage) command
value
Yes Yes Yes Yes 6-27
2
Auxiliary frequency reference (is
used as frequency reference 2)
Maximum output frequency Yes Yes Yes Yes 6-7
4 Voltage bias Motor rated voltage (E1-05) Yes Yes No No -
5 Accel/decel time gain
Set acceleration and deceleration times (C1-
01 to C1-08)
Yes Yes Yes Yes 6-21
6 DC injection braking current Inverter rated output current Yes Yes Yes No 6-18
7
Overtorque/undertorque detection
level
Motor rated torque for vector control
Inverter rated output current for V/f control
Yes Yes Yes Yes 6-48
8 Stall prevention level during run Inverter rated output current Yes Yes No No 6-45
9 Frequency reference lower limit level Maximum output frequency Yes Yes Yes Yes 6-30
A Jump frequency Maximum output frequency Yes Yes Yes Yes 6-29
B PID feedback Maximum output frequency Yes Yes Yes Yes 6-96
C PID target value Maximum output frequency Yes Yes Yes Yes 6-96
D Frequency bias 2 Maximum output frequency Yes Yes Yes Yes
E Motor temperature input Yes Yes Yes Yes 6-50
10 Positive torque limit Motor's rated torque No No Yes Yes 6-43
11 Negative torque limit Motor's rated torque No No Yes Yes 6-43
12 Regenerative torque limit Motor's rated torque No No Yes Yes 6-43
13
Torque reference/torque limit at
speed control
Motor’s rated torque No No No Yes 6-118
14 Torque compensation Motor’s rated torque No No No Yes 6-118
15 Positive/negative torque limit Motor's rated torque No No Yes Yes 6-43
1F Analog input not used. Yes Yes Yes Yes