User`s manual

5-47
5
Multi-function Analog Outputs: H4
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
H4-01
Monitor
selection
(terminal
FM)
Sets the number of the moni-
tor item to be output (U1-
) at terminal FM.
The monitors U1-04, -10 to
-14, -28, -34, -39, -40 cannot
be set to output at terminal
FM)
1 to 38 2 No A A A A 41DH 6-77
Terminal
FM Sel
H4-02
Gain (termi-
nal FM)
Sets the multi-function analog
output 1 (terminal FM) gain.
Sets the percentage of the
monitor item that is equal to
10V/20mA output at terminal
FM. Note that the maximum
output voltage/current is 10V/
20mA.
0 to
1000.0
%
100% Yes Q Q Q Q 41EH
4-5
6-77
Terminal
FM Gain
H4-03
Bias (termi-
nal FM)
Sets the multi-function analog
output 1 (terminal FM) bias.
Sets the percentage of the
monitor item that is equal to
0V/4mA output at terminal
FM.
The maximum output from the
terminal is 10 V/20mA.
-110 to
+110%
0.0% Yes A A A A 41FH 6-77
Terminal
FM Bias
H4-04
Monitor
selection
(terminal
AM)
Sets the number of the moni-
tor item to be output (U1-
) at terminal AM.
The monitors U1-04, -10 to
-14, -28, -34, -39, -40 cannot
be set to be output at terminal
AM).
1 to 38 3 No A A A A 420H 6-77
Terminal
AM Sel
H4-05
Gain (termi-
nal AM)
Set the multi-function analog
output 2 (terminal AM) gain.
Sets the percentage of the
monitor item that is equal to
10V/20mA output at terminal
AM. Note that the maximum
output voltage/current is 10V/
20mA.
0 to
1000.0
%
50.0% Yes Q Q Q Q 421H
4-5
6-77
Terminal
AM Gain
H4-06
Bias (termi-
nal AM)
Sets the multi-function analog
output 2 (terminal AM) bias.
Sets the percentage of the
monitor item that is equal to
0V/4mA output at terminal
AM.
The maximum output from the
terminal is 10 V/20mA.
-110.0
to
+110.0
%
0.0% Yes A A A A 422H 6-77
Terminal
AM Bias
H4-07
Analog out-
put 1 signal
level selec-
tion
Sets the signal output level for
multi-function output 1 (ter-
minal FM)
0: 0 to +10 V output
1: –10V to +10V output
2: 4 – 20 mA
Switch current and voltage
output using CN15 on the
control panel
0 to 2 0 No A A A A 423H 6-77
AO Level
Select1