User`s manual

5-48
5
MEMOBUS Communications: H5
* Set H5-01 to 0 to disable Inverter responses to MEMOBUS communications.
H4-08
Analog out-
put 2 signal
level selec-
tion
Sets the signal output level for
multi-function output 2 (ter-
minal AM)
0: 0 to +10 V output
1: –10V to +10V output
2: 4 – 20 mA
Switch current and voltage
output using CN15 on the
control panel
0 to 2 0 No A A A A 424H 6-77
AO Level
Select2
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
H5-01
Station
address
Sets the Inverter's node
address.
0 to 20
*
1F No A A A A 425H 6-80
Serial
Comm Adr
H5-02
Communica-
tions speed
selection
Sets the baud rate for MEMO-
BUS communications.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
0 to 4
3NoAAAA426H6-80
Serial Baud
Rate
H5-03
Communica-
tions parity
selection
Sets the parity for MEMO-
BUS communications.
0: No parity
1: Even parity
2: Odd parity
0 to 2 0 No A A A A 427H 6-80
Serial Com
Sel
H5-04
Stopping
method after
communica-
tions error
Sets the stopping method for
communications errors.
0: Deceleration to stop using
the deceleration time in
C1-02
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-09
3: Continue operation
0 to 3 3 No A A A A 428H 6-80
Serial Fault
Sel
H5-05
Communica-
tions error
detection
selection
Sets whether or not a commu-
nications time-out is to be
detected as a communications
error.
0: Do not detect.
1: Detect
0 or 1 1 No A A A A 429H 6-80
Serial Flt
Dtct
H5-06
Send wait
time
Sets the time from the Inverter
receiving data to when the
Inverter starts to send.
5 to 65 5 ms No A A A A 42AH 6-80
Transmit
WaitTIM
H5-07
RTS control
ON/OFF
Enables or disables RTS con-
trol.
0: Disabled (RTS is always
ON)
1: Enabled (RTS turns ON
only when sending)
0 or 1 1 No A A A A 42BH 6-80
RTS Con-
trol Sel
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display