* The factory setting depends upon the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
N: Special Adjustments
Hunting Prevention Function: N1
L8-11
Cooling fan
control delay
time
Set the time in seconds to
delay turning OFF the cooling
fan after the inverter STOP
command is given.
0 to 300 60 s No A A A A 4B7H 6-61
Fan Delay
Time
L8-12
Ambient
temperature
Sets the ambient temperature. 45 to 60 45 °CNo A A A A 4B8H6-62
Ambient
Temp
L8-15
OL2 charac-
teristics
selection at
low speeds
0: OL2 characteristics at low
speeds disabled.
1: OL2 characteristics at low
speeds enabled.
It is not recommended to use
another setting than the fac-
tory setting.
0 or 1 1 No A A A A 4BBH 6-63
OL2 Sel @
L-Spd
L8-18
Soft CLA
selection 0: Disable
1: Enable
0 or 1 0 No A A A A 4BFH -
Soft CLA Sel
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
N1-01
Hunting-pre-
vention
function
selection
0: Hunting-prevention
function disabled
1: Hunting-prevention
function enabled
The hunting-prevention func-
tion suppresses hunting when
the motor is operating with a
light load.
If high response has the prior-
ity over vibration suppres-
sion, disable the hunting-
prevention function.
0 or 1 1 No A A No No 580H 6-41
Hunt Prev
Select
N1-02
Hunting-pre-
vention gain
Sets the hunting-prevention
gain.
Normally, there is no need to
change this setting.
If necessary, make the adjust-
ments as follows:
• If vibration occurs with
light load, increase the set-
ting.
• If the motor stalls, reduce
the setting.
If the setting is too large, the
voltage will be too suppressed
and the motor may stall.
0.00 to
2.50
1.00 No A A No No 581H
4-14
6-41
Hunt Prev
Gain
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector