User`s manual
5-74
5
Parameter Initial Values that Change With the Setting of C6-01
Parame-
ter Num-
ber
Name Unit Factory Setting
- Inverter Capacity kW 160 185 220 300
o2-04 kVA selection - 34 35 36 37
b8-03
Energy-saving filter time
constant
s 2.00 (Open Loop vector)
b8-04 Energy-saving coefficient -
30.13 30.57 27.13 21.76
E2-01
(E4-01)
Motor rated current A
270.0 310.0 370.0 500.0
E2-02
(E4-02)
Motor rated slip Hz 1.35 1.30 1.30 1.25
E2-03
(E4-03)
Motor no-load current A
70.0 81.0 96.0 130.0
E2-05
(E4-05)
Motor line-to-line resis-
tance
W
0.029 0.025 0.020 0.014
E2-06
(E4-06)
Motor leak inductance % 20.0 20.0 20.0 20.0
E2-10
Motor iron loss for torque
compensation
W
2850 3200 3700 4700
L2-02
Momentary power loss ride
through time
- 2.0 2.0 2.0 2.0
L2-03 Min. baseblock (BB) time s 1.8 1.9 2.0 2.1
L2-04 Voltage recovery time s 1.0 1.0 1.0 1.0
L8-02 Overheat pre-alarm level °C 108 95 100 95
Parameter
Number
Name
Initial Value
C6-01=0 (Heavy Duty) C6-01=1 or 2 (Normal Duty 1 or 2)
C6-02 Carrier frequency selection 1
Depends on the inverter rated
power
L3-02 Stall prevention at acceleration level 150% 120%
L3-06 Stall prevention during running operation level 150% 120%
L8-15 OL2 characteristics at low speed 0 (Disabled) 1 (Enabled)