User`s manual
6-19
6
Acceleration and Deceleration Characteristics
Setting Acceleration and Deceleration Times
The acceleration time indicates the time to increase the output frequency from 0% to 100% of the maximum
output frequency (E1-04). The deceleration time indicates the time to decrease the output frequency from
100% to 0% of (E1-04). The accel./decel. times 1 are used with the factory setting, the accel./decel. times 2 to
4 can be selected using a multifunction digital input.
Related Parameters
Multi-function Digital Inputs (H1-01 to H1-05)
Setting Acceleration and Deceleration Time Units
Set the acceleration/deceleration time units using C1-10. The factory setting is 1.
Parameter
No.
Name
Factory
Setting
Change
during
Opera-
tion
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Closed
Loop
Vector
C1-01 Acceleration time 1
10.0 s
YesQQQQ
C1-02Deceleration time 1 Yes QQQQ
C1-03Acceleration time 2 Yes AAAA
C1-04Deceleration time 2 Yes AAAA
C1-05Acceleration time 3 No AAAA
C1-06Deceleration time 3 No AAAA
C1-07Acceleration time 4 No AAAA
C1-08Deceleration time 4 No AAAA
C1-10Acceleration/deceleration time setting unit 1 No AAAA
C1-11Acceleration/deceleration time switching frequency 0.0 HzNo AAAA
C2-01 S-curve characteristic time at acceleration start 0.20 s No AAAA
C2-02 S-curve characteristic time at acceleration end 0.20 s No AAAA
C2-03 S-curve characteristic time at deceleration start 0.20 s No AAAA
C2-04 S-curve characteristic time at deceleration end 0.00 s No AAAA
Set
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
7 Acceleration/Deceleration time 1 Yes Yes Yes Yes
1A Acceleration/Deceleration time 2 Yes Yes Yes Yes
Set value Details
0 The acceleration/deceleration time setting range is 0.00 to 600.00 in units of 0.01 s.
1 The acceleration/deceleration time setting range is 0.00 to 6000.0 in units of 0.1 s.