User`s manual

6-25
6
Setting Example
An example of stall prevention during deceleration when L3-04 is set to 1 is shown below.
Fig 6.28 Stall Prevention During Deceleration Operation
Setting Precautions
The stall prevention level during deceleration differs depending on the inverter rated voltage and input
voltage. Refer to the following table for details.
When using the braking option (braking resistor, braking resistor units, and braking units), be sure to set
parameter L3-04 to 0 or 3.
When a braking option is used and the deceleration time shall be optimized (shorter than setting of C1-02/
04/06/08), L3-04 has to be set to 3.
Inverter Rated/Input Voltage Stall Prevention Level during Deceleration (V)
200 V class 380
400 V class
E1-01 400 V 760
E1-01 < 400 V 660
Deceleration time controlled to
prevent overvoltage
Deceleration time
(set value)
Time