Inverter Overheat Protection
The Inverter is protected against overheating using a thermistor that detects the heatsink temperature.
When the overheat temperature level is reached the inverter output is switched off.
To prevent a suddenly and unexpected stop of the inverter due to an over temperature, an overheating pre-
alarm can be output. The temperature level for that pre-alarm can be set in parameter L8-02. Using parameter
L8-03 the inverter operation when an over temperature occurs can be selected.
If a multifunction output is programmed for this function the output is switched ON when the heatsink temper-
ature exceeds the overheat pre-alarm level set in L8-02.
Related Parameters
Multifunction Outputs (H2-01 to H2-03)
Input Open Phase Protection
For the Input Phase Loss Detection the drive monitors the DC bus ripple. The drive integrates this ∆V value
over 10 scans (approximately 10 seconds). If the integrated ∆V value of any consecutive ten scan range is
greater than the voltage determined by multiplying L8-06 times the drives rated OV Trip point (400Vdc/
800Vdc), a PF fault will occur and the Drive will coast to stop
Fig 6.63 Input Phase Loss Detection
Related Parameters
Generally it is not recommended to disable this function.
Parameter
No.
Name
Factory
Setting
Change
during
Opera-
tion
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Closed
Loop
Vector
L8-02 Overheat pre-alarm level 95°C No AAAA
L8-03Inverter overheat (OH) pre-alarm operation selection 3 No AAAA
Set Value Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
20 Inverter overheat (OH) Yes Yes Yes Yes
Parameter
No.
Name
Factory
Setting
Change
during
Opera-
tion
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Closed
Loop
Vector
L8-05Input open-phase protection selection 1 No AAAA
t
L8-06
Phase Loss Fault
Signal
DC Bus
Voltage
10 seconds