User`s manual

6-66
6
Drive Enable/Disable
If a digital input is programmed for this function (H1-=6A) the drive can be enabled or disabled by
switching the digital input ON/OFF (ON – Drive enabled).
If the input is switched OFF while a RUN command is active the inverter will stop using the stopping method
set in b1-03.
Stopping Acceleration and Deceleration (Acceleration/Deceleration
Ramp Hold)
A multi-function input can be used to pause the acceleration or deceleration and maintain (hold) the output
frequency. To program one digital input for this function one of the parameters H1-01 to H1-05 has to be
set to 6A.
The acceleration/deceleration is hold when the input is turned ON.
The acceleration/deceleration is restarted when the acceleration/deceleration ramp hold input is turned
OFF.
The motor will be stopped if a stop command is input while the acceleration/deceleration ramp hold input
is ON.
When parameter d4-01 (the frequency reference hold function selection) is set to 1, the held frequency will
be stored in memory. This stored frequency will be retained as frequency reference even after a power loss
and the motor will be restarted at this frequency when a run command is input again.
Related Parameters
Multi-function Digital Inputs (H1-01 to H1-05)
Set
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
6A Enable/Disable drive (ON: drive enabled) Yes Yes Yes Yes
Parameter
No.
Name
Factory
Setting
Change
during
Opera-
tion
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Closed
Loop
Vector
d4-01Frequency reference hold function selection 0 No AAAA
Set Value Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
A Acceleration/deceleration ramp hold (ON: hold is active) Yes Yes Yes Yes