User`s manual

6-72
6
Switching Operation Source to Communication Option Card
The source of frequency reference and RUN command can be switched between a Communication option
card and the sources selected in b1-01 and b1-02. Set one of the parameters H1-01 to H1-05 (digital inputs S3
to S7 function selection) to 2 to enable operation source switch over.
If a RUN command is active, the switch over will not be accepted.
Related Parameters
Multi-function Digital Inputs (H1-01 to H1-05)
Setting Precautions
To use the operation source switching function make the following settings:
Set b1-01 (frequency reference source) to a value different from 3 (option card).
Set b1-02 (RUN command source) to a value different from 3 (option card).
Set one of the parameters H1-01 to H1-02 to 2.
Jog Frequency with Direction Commands (FJOG/RJOG)
The FJOG/RJOG function operates the inverter at the jog frequency. It can be activated by using the terminal
ON/OFF operation. When using the FJOG/RJOG commands, there is no need to input the RUN command.
To use this function, set one of the parameters H1-01 to H1-05 (digital input terminal S3 to S7 function selec-
tion) to 12 (FJOG command) or 13 (RJOG command).
Related Parameters
Multi-Function Digital Inputs (H1-01 to H1-05)
Application Precautions
Jog frequencies using FJOG and RJOG commands have the priority over other frequency references.
When both FJOG command and RJOG commands are ON for 500 ms or longer at the same time, the
Inverter stops according to the setting in b1-03 (stopping method selection).
Set Value Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
2
Operation source selection: Option Card/ Inverter (ON: Inverter settings in b1-01 and b1-
02, OFF: Option Card)
Yes Yes Yes Yes
Parameter
No.
Name
Factory
Setting
Change
during
Opera-
tion
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Closed
Loop
Vector
d1-17 Jog frequency reference 6.00 Hz Yes QQQQ
Set Value Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes