User`s manual

3-12
3
The following example shows the autotuning input procedure for standard rotating autotuning in Open Loop
Vector Control.
Fig 3.8 Operation in Autotuning Mode
If a fault occurs during autotuning, refer to Chapter 7 Troubleshooting.
START GOAL
** Main Menu **
-DRIVE-
Operation
** Main Menu **
-QUICK-
Quick Setting
** Main Menu **
-ADV-
Programming
** Main Menu **
-VERIFY-
Modified Consts
** Main Menu **
-A.TUNE-
Auto-Tuning
Monitor Display Setting DisplayMode Selection Display
Tuning Mode Sel
-A.TUNE-
T1- 01 =0 *0*
Auto-Tuning
-A.TUNE-
Press RUN key
Tuning Ready ?
Tune Proceeding
-A.TUNE-
40.0Hz/10.5A
Standard Tuning
Tuning Mode Sel
-A.TUNE-
01 = 0*0*
Rated Frequency
-A.TUNE-
T1- 05 = 50.0Hz
Rated Speed
-A.TUNE-
T1- 07 = 1750RPM
Rated Frequency
-A.TUNE-
T1-05
=
050.0Hz
Rated Speed
-A.TUNE-
Rdy
Tune Aborted
-A.TUNE-
STOP key
The display will
automatically
change depending
on the status of
autotuning.
Standard Tuning
START GOAL
Tune Proceeding
-A.TUNE-
40.0Hz/10.5A
Tune Successful
-A.TUNE-
Tune Successful
Tune Proceeding
-A.TUNE-
"0"
"0"
0.0Hz/0.0A
MENU
ESC
MENU
MENU
MENU
MENU
MENU
ESC
ESC
ESC
RUN
STOP
(0.0~400.0)
"50.0Hz"
(0.0~400.0)
"50.0Hz"
(0~24000)
"1750"
Mtr Rated Power
-A.TUNE-
T1- 02= 0.40kW
Mtr Rated Power
-A.TUNE-
T1-01=
0 00.40kW
"0.40kW"
ESC
Rated Voltage
-A.TUNE-
T1- 03 = 200.0VAC
Rated Voltage
-A.TUNE-
ESC
Rated Current
-A.TUNE-
Rated Current
-A.TUNE-
ESC
(0.00~650.00)
"0.40kW"
(0.00~650.00)
"200.0VAC"
(0.0~255.0)
"200.0VAC"
(0.0~255.0)
T1- 03 = 200.0VAC
T1- 04 = 1.90A
"1.90A"
(0.32~6.40)
T1- 04 = 001.90A
"1.90A"
(0.32~6.40)
Number of Poles
-A.TUNE-
T1- 06 = 4
Number of Poles
-A.TUNE-
T1-06 = 4
(2~48)
"4"
(2~48)
"4"
T1-
07
= 01750RPM
(0~24000)
"1750"