YASKAWA VS-606V7 Series INSTRUCTION MANUAL COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL) Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference. MANUAL NO.
PREFACE YASKAWA’s VS-606V7 is a small and simple inverter; as easy as using a contactor. This instruction manual describes installation, maintenance and inspection, troubleshooting, and specifications of the VS-606V7. Read this instruction manual thoroughly before operation. YASKAWA ELECTRIC CORPORATION General Precautions • Some drawings in this manual are shown with the protective cover or shields removed in order to describe detail with more clarity.
NOTES FOR SAFE OPERATION Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the VS-606V7. In this manual, NOTES FOR SAFE OPERATION are classified as “WARNING” or “CAUTION.” WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury to personnel. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury to personnel or damage to equipment.
WARNINGS FOR UL/cUL MARKING • Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON. • The Inverter internal capacitor is still charged even after the power supply is turnd OFF. To prevent electric shock, disconnect all power before servicing the Inverter. Then wait at least one minute after the power supply is disconnected and all indecators are OFF. • Do not perform a withstand voltage test on any part of the Inverter.
RECEIVING CAUTION (Ref. page) • Do not install or operate any inverter which is damaged or has missing parts. Failure to observe this caution may result in personal injury or equipment damage.÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷16 MOUNTING CAUTION (Ref. page) • Lift the cabinet by the cooling fin. When moving the unit, never lift by the plastic case or the terminal covers. Otherwise, the main unit may be dropped causing damage to the unit.
WIRING WARNING (Ref. page) • Only commence wiring after verifying that the power supply is turned OFF. Failure to observe this warning can result in an electric shock or a fire.÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷24 • Wiring should be performed only by qualified personnel. Failure to observe this warning can result in an electric shock or a fire.÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷÷24 • When wiring the emergency stop circuit, check the wiring thoroughly before operation.
CAUTION (Ref. page) • Verify that the inverter rated voltage coincides with the AC power supply voltage. Failure to observe this caution can result in personal injury or a fire. • Do not perform a withstand voltage test of the inverter. It may cause semi-conductor elements to be damaged. • To connect a braking resistor, braking resistor unit or braking unit, follow the procedures described in this manual. Improper connection may cause a fire.
OPERATION WARNING (Ref. page) • Only turn ON the input power supply after replacing the digital operator/blank cover (optional). Do not remove the digital operator or the covers while current is flowing. Failure to observe this warning can result in an electric shock. • Never operate the digital operator or dip switches when your hand is wet. Failure to observe this warning can result in an electric shock. • Never touch the terminals while current is flowing, even during inverter is stopping.
CAUTION (Ref. page) • Never touch the heatsink since the temperature is very high. Failure to observe this caution can result in harmful burns to the body. • Since it is easy to change operation speed from low to high, verify the safe working range of the motor and machine before operation. Failure to observe this caution can result in personal injury and machine damage. • Install a holding brake separately if necessary. Failure to observe this caution can result in personal injury.
WARNING (Ref. page) • Do not perform withstand voltage test on any part of the VS-606V7. This electronic equipment uses semiconductors and is vulnerable to high voltage. • Only authorized personnel should be permitted to perform maintenance, inspections or parts replacement. [Remove all metal objects (watches, bracelets, etc.) before operation.] (Use tools which are insulated against electrical shock.) Failure to observe this warning can result in an electric shock.÷÷÷÷÷÷131 CAUTION (Ref.
WARNING DISPLAY A warning label is displayed on the front cover of the inverter, as shown below. Follow these instructions when handling the inverter.
CONTENTS NOTES FOR SAFE OPERATION••••••••••••••••••••••••••••••3 1. RECEIVING•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••16 Checking the Name Plate ••••••••••••••••••••••••••••••••••••••••••••••16 2. IDENTIFYING THE PARTS ••••••••••••••••••••••••••••••••••17 3.
Operating at low speed •••••••••••••••••••••••••••••••••••••••••••••••52 Adjusting speed setting signal ••••••••••••••••••••••••••••••••••••••53 Adjusting frequency upper and lower limits •••••••••••••••••••••••54 Using four accel/decel times ••••••••••••••••••••••••••••••••••••••••••55 Automatic restart after momentary power loss •••••••••••••••••••56 Soft-start characteristics ••••••••••••••••••••••••••••••••••••••••••••••••57 Torque detection •••••••••••••••••••••••••••••••••••••••••••••••••••••••••58 Fr
Selecting Cooling Fan Operation •••••••••••••••••••••••••••••••••••••89 Using MEMOBUS (MODBUS) Communications ••••••••••••••••89 MEMOBUS(MODBUS) communications •••••••••••••••••••••••••••89 Communication specifications ••••••••••••••••••••••••••••••••••••••••90 Communication connection terminal ••••••••••••••••••••••••••••••••90 Procedure for communications with PLC ••••••••••••••••••••••••••90 Setting constants necessary for communication ••••••••••••••••91 Message format ••••••••••••••••••••••••••••••
7. MAINTENANCE AND INSPECTION ••••••••••••••••131 Periodical Inspection ••••••••••••••••••••••••••••••••••••••••••••••••••131 Part Replacement •••••••••••••••••••••••••••••••••••••••••••••••••••••131 8. FAULT DIAGNOSIS •••••••••••••••••••••••••••••••••••••••••••134 Protective and Diagnostic Function •••••••••••••••••••••••••••••••••134 Troubleshooting••••••••••••••••••••••••••••••••••••••••••••••••••••••••••143 9.
1. RECEIVING After unpacking the VS-606V7, check the following : ▫ Verify that the part numbers match your purchase order or packing slip. ▫ Check the unit for physical damage that may have occurred during shipping. If any part of VS-606V7 is missing or damaged, call for service immediately. Checking the Name Plate Example of 3-phase, 200VAC, 0.1kW (0.13HP) INVERTER MODEL INPUT SPEC. OUTPUT SPEC. LOT NO. SERIAL NO. MODEL MASS SOFTWARE NO. CIMR —V 7AC20P1 Inverter VS-606V7 Series No.
2. IDENTIFYING THE PARTS DIGITAL OPERATOR TERMINAL COVER WIRING HOLES FOR CONTROL CIRCUIT FRONT COVER WIRING HOLES FOR MAIN CIRCUIT GROUND TERMINAL TOP COVER NAME PLATE HEATSINK COOLING FAN FAN COVER BOTTOM COVER DIGITAL OPERATOR JVOP-147 DIGITAL OPERATOR JVOP-140 FREF FOUT F/R MNTR FREF PRGM F/R FOUT DSPL RUN MIN MAX STOP RESET Digital operator (with potentiometer) JVOP-140 Used for setting or changing constants. Frequency can be set using potentiometer.
VS-606V7 inverters with the covers removed DIGITAL OPERATOR JVOP-140 FREF FOUT F/R DSPL DATA ENTER IOUT MNTR LO/RE PRGM < > INPUT POLARITY SWITCH FREQUENCY SETTING POTENTIOMETER STATUS DISPLAY LAMP TERMINAL RESISTOR SWITCH FOR COMMUNICATION CIRCUIT RUN MAX MIN STOP RESET VOLTAGE/CURRENT CHANGE SWITCH FOR ANALOG FREQUENCY REFERENCE INPUT OMRON G5S 1 2 12 13 14 SHORT CIRCUIT BAR CONTROL CIRCUIT TERMINAL BLOCK 22 1 2 3 11 MAIN CIRCUIT TERMINAL BLOCK GROUND TERMINAL Example of 3-phase (20
Main Circuit Terminal Arrangement Terminal arrangement of the main circuit terminal differs depending on the inverter model.
3. MOUNTING Choosing a Location to Mount the Inverter Be sure the inverter is protected from the following conditions : ▫ Extreme cold and heat. Use only within the ambient temperature range : -10 to +50; (14 to 122,) for IP20 (open chassis type), -10 to +40˚C (14 to 105˚F) for NEMA 1 (TYPE 1), IP 20 (Top-closed type) ▫ Rain, moisture ▫ Oil sprays, splashes ▫ Salt spray ▫ Direct sunlight. (Avoid using outdoors) ▫ Corrosive gases (e.g. sulfurized gas) or liquids ▫ Dust or metallic particles in the air.
Mounting Dimensions To mount the VS-606V7, dimensions as shown below are required. 30mm (1.18 in.) OR MORE 30mm (1.18 in.) OR MORE AIR 100mm (3.94 in.) OR MORE AIR 100mm (3.94 in.
Mounting / Removing Components Removing and Mounting Digital Operator and Covers • Removing front cover Use a driver to loosen the screw on the front cover surface to direction 1 to remove it. Then press the right and left sides to direction 2 and lift the front cover to direction 3. • Mounting front cover Mount the front cover in the descending order of the above procedure for removal.
• Removing digital operator After removing the front cover, lift the upper and lower sides (section A) of the right side of the digital operator to direction 1. • Mounting digital operator Mount the digital operator in the descending order of the above procedure for removal. • Removing bottom cover After removing the front cover and the terminal cover, tilt the bottom cover to direction 1 with section A as a supporting point.
4. WIRING Wiring Instructions (1) Always connect the power supply (for main circuit inputs) and power input terminals R/L1, S/L2, and T/L3 (R/L1, S/L2 for single-phase) via a molded-case circuit breaker (MCCB) or a fuse. Never connect them to terminals U/T1,V/T2,W/T3, B1, B2, -, +1, or +2. The inverter may be damaged. Refer to page 148 for Recommended Peripheral Devices. For single-phase inverters, always use terminal R/L1 and S/L2. Never connect to terminal T/L3.
(10) Voltage drop should be considered when determining wire size. Voltage drop can be calculated using the following equation: Phase-to phase voltage drop (V) = √3 wire resistance (Ω/km) × wiring distance (m) × current (A) × 10-3 Select a wire size so that voltage drop will be less than 2% of the normal rated voltage. Wire and Terminal Screw Sizes 1.
200V Class Single-phase Input Series Tightening Terminal Applicable size Torque Model Symbol Screw • • N m (lb in) mm2 AWG Wire Recommended size mm2 AWG CIMRV7*C B0P1 R/L1,S/L2,T/L3, –,+1,+2,B1,B2, U/T1,V/T2,W/T3 M3.5 0.8 to 1.0 0.75 to 2 (7.1 to 8.88) 18 to 14 2 14 CIMRV7*C B0P2 R/L1,S/L2,T/L3, –,+1,+2,B1,B2, U/T1,V/T2,W/T3 M3.5 0.8 to 1.0 0.75 to 2 (7.1 to 8.88) 18 to 14 2 14 CIMRV7*C B0P4 R/L1,S/L2,T/L3, –,+1,+2,B1,B2, U/T1,V/T2,W/T3 M3.5 0.8 to 1.0 0.75 to 2 (7.1 to 8.
400V Class 3-phase Input Series Tightening Terminal Torque Symbol Screw N • m (Ib • in) Model Applicable size mm2 AWG Wire Recommended size mm2 AWG CIMRV7*C 40P2 R/L1,S/L2,T/L3, –,+1,+2,B1,B2, U/T1,V/T2,W/T3 M4 1.2 to 1.5 2 to 5.5 (10.65 to 13.31) 14 to 10 2 14 CIMRV7*C 40P4 R/L1,S/L2,T/L3, –,+1,+2,B1,B2, U/T1,V/T2,W/T3 M4 1.2 to 1.5 2 to 5.5 (10.65 to 13.31) 14 to 10 2 14 CIMRV7*C 40P7 R/L1,S/L2,T/L3, –,+1,+2,B1,B2, U/T1,V/T2,W/T3 M4 1.2 to 1.5 2 to 5.5 (10.65 to 13.
Wiring the Main Circuit L1L2 L3 [Example of 3-phase, 400V class, 0.37kW inverters] MCCB or leakage breaker • Main circuit input power supply Always connect the power supply line to input terminals R/L1, S/L2, and T/L3 [R/L1, S/L2 for single-phase inverters]. Never connect them to terminal U/T1,V/T2,W/T3, B1, B2, -, +1, or +2. Otherwise the inverter may be damaged. NOTE For single-phase inverters, always use terminals R/L1 and S/L2. Never connect to terminal T/L3. • Grounding (Use ground terminal .
Wiring the Control Circuit Only basic insulation is provided for the control circuit terminals. Additional insulation may be necessary in the end product. • Control Circuit terminals Pass the cable through wiring hole and connect. Be sure to mount the covers on the original position.
Open the front cover and verify that the strip length is 5.5mm (0.22in.). 5.5 mm SCALE MA MBMC CONTACT OUTPUT S5 S6 S7 P1 P2 R R FS FR FC S1 S2 S3 S4 SC PC S S AM AC RP SW1 SW2 Wiring Inspection After completing wiring, check the following : ▫ Wiring is proper. ▫ Wire clippings or screws are not left in the unit. ▫ Screws are securely tightened. ▫ Bare wire in the terminal does not contact other terminals.
5. OPERATING THE INVERTER Initial setting of control mode selection (n002) is set at V/f control mode. Test Run The inverter operates by setting the frequency (speed). There are four types of operation modes for the VS-606V7 : 1 Run command from the digital operator (potentiometer/digital setting). 2 Run command from the control circuit terminal. 3 Run command from communications (MEMOBUS communications).
Operator Display Operation Steps 1. Turn ON the power supply. 2. Set constant n004 to 1. 6.00 Examine the application. (Never select REV when reverse run is prohibited.) 5. Set the reference by pressing q or w key. NOTE RUN ALARM PRGM RUN ALARM PRGM RUN ALARM F/R RUN ALARM FREF RUN ALARM FOUT RUN ALARM FOUT RUN ALARM : Blinking (Long Blinking) : Blinking 15.0 5.0 (Forward) or (Reverse) 60.00 6. Press RUN . 0.00➝60.00 7. Press STOP to stop. 60.00➝0.
Operating the Digital Operator All functions of the VS-606V7 are set by the digital operator. Below are descriptions of the display and keypad sections. DIGITAL OPERATOR JVOP-140 Data display section Display section Function display LED’s LED switches to another function each time DSPL is pressed. The displayed data can be changed. FREF FOUT IOUT F/R RUN > DSPL MNTR LO/RE PRGM < Press to switch between function LEDs.
Description of Status Indicator LEDs There are two LEDs on the middle right section of the face of the VS-606V7. The inverter status is indicated by various combinations of ON, BLINKING and OFF LEDs. RUN indicator and status indicator on the RUN button have the same function.
LED Description By pressing DSPL on the digital operator, each of the function LEDs can be selected. The following flowchart describes each function LED. Power ON FREF Frequency reference setting/monitor (Hz) Sets VS-606V7 operation speed. DSPL FOUT Output frequency monitor (Hz) Displays frequency that VS-606V7 is currently outputting. Setting disabled. DSPL IOUT Output current monitor (A) Displays current that VS-606V7 is currently outputting. Setting disabled.
LOCAL / REMOTE Selection < This function switches the operation; operation using the digital operator including frequency setting with potentiometer, or that using the input terminals or through communications Setting can be changed by or key. (Local) < LO/RE (Remote) DSPL Constant No. / data PRGM Sets and changes data using constant No. (Refer to page 39.) DSPL Return to MNTR FREF Multi-Function monitor • Selecting monitor Press DSPL key.
• Monitoring Following items can be monitored by U- constants. Constant No. Name U-01 Frequency reference (FREF)*1 Hz Frequency reference can be monitored. (Same as FREF) U-02 Output frequency (FOUT)*1 Hz Output frequency can be monitored. (Same as FOUT) U-03 Output current (IOUT)*1 A Output current can be monitored. (Same as IOUT) U-04 Output voltage V Output voltage can be monitored. U-05 DC voltage V Main circuit DC voltage can be monitored.
Input / Output terminal status Input terminal status 1: Terminal S1 is “closed.” 1: Terminal S2 is “closed.” 1: Terminal S3 is “closed.” 1: Terminal S4 is “closed.” 1: Terminal S5 is “closed.” 1: Terminal S6 is “closed.” 1: Terminal S7 is “closed.” Not used Output terminal status 1: Terminal MA-MC is “closed.” 1: Terminal P1-PC is “closed.” 1: Terminal P2-PC “closed.
Fault history display method When U-09 is selected, a four-digit box is displayed. The three digits from the right show the fault description, and the digit on the left shows the order of fault (from one to four). Number 1 represents the latest fault, and 2,3,4, in ascending order of fault occurrence. (Example) ?? •••••• 4-digit numbers < : Order of fault (1 to 4) ??? : Fault description "---" is displayed if there is no fault. (Refer to page 134 for details.
Simple Data Setting Digital setting (Refer to 5. OPERATING THE INVERTER) and potentiometer setting are both available for simple accel/decel operation of the VS-606V7. Digital setting is set at the factory (n004=1). For the model with digital operator (with potentiometer) JVOP-140, factory setting is set by frequency setting potentiometer (n004=0). Following is an example in which the function LED’s are used to set frequency reference, acceleration time, deceleration time, and motor direction.
6. PROGRAMMING FEATURES Factory settings of the constants are shown as in the tables. Constant Set-up and Initialization Constant selection/initialization (n001) The following table describes the data which can be set or read when n001 is set. Unused constants among n001 to n179 are not displayed.
Using V/f Control Mode V/f control mode is preset at the factory. Control mode selection (n002)= 0: V/f control mode (initial setting) 1: Vector control mode Adjusting torque according to application Adjust motor torque by using “V/f pattern” and “full-range automatic torque boost”. • V/f pattern setting Set V/f pattern by n011 to n017 as described below. Set each pattern when using a special motor (high-speed motor, etc.) or when requiring special torque adjustment of machine.
• Typical setting of V/f pattern Set the V/f pattern according to the application as described below. For 400V class, the voltage values (n012, n015, and n017) should be doubled. When running at a frequency exceeding 50Hz/60Hz, change the maximum output frequency (n011). Note :Be sure to set the maximum output frequency according to the motor characteristics.
• Full-range automatic torque boost (when V/f mode is selected; n002=0) Motor torque requirement changes according to load conditions. Fullrange automatic torque boost adjusts voltage of V/f pattern according to the requirement. The VS-606V7 automatically adjusts the voltage during constant-speed operation as well as during acceleration. The required torque is calculated by the inverter. This ensures tripless operation and energy-saving effects.
Using Vector Control Mode Setting the control mode selection (n002) can use a vector control mode. n002 = 0: V/f control mode (factory setting) 1: Vector control mode Precaution for voltage vector control application Since vector control needs motor constants, the YASKAWA standard motor constants have been set at the factory prior to shipment.
Select slip compensation status during regeneration: n113 Setting Slip correction during regenerative operation Disabled 0 Enabled 1 Motor constant calculation Following show an example of motor constant calculation. (1) Motor rated slip (n106) 120 × motor rated frequency (Hz)*1 = Number of motor pole – Motor rated speed (r/min)*2 120 / Number of motor pole (2) Line to neutral (per phase) (n107) Calculations are based on line-to-line resistance and insulation grade of the motor test report.
V/f pattern during vector control Set V/f pattern as follows during vector control. The following examples are for 200V class motors. When using 400V class motors, double the voltage settings (n012, n015, n017). STANDARD V/F (V) 200 (V) 200 [MOTOR SPECIFICATION: 60Hz] 11 [MOTOR SPECIFICATION: 50Hz] 11 4.3 4.3 1 3 60 (Hz) 0.8 2.5 50 (Hz) HIGH STARTING TORQUE V/F (V) 200 [MOTOR SPECIFICATION: 60Hz] (V) 200 13 [MOTOR SPECIFICATION: 50Hz] 13 5 5 1 3 60 (Hz) 0.8 2.
Switching LOCAL/REMOTE Modes The following functions can be selected by switching the LOCAL or REMOTE mode. To select RUN/STOP commands or frequency reference, change the mode in advance depending on the following applications. • LOCAL mode: Enables the digital operator for RUN/STOP c o m m a n d s a n d F W D / R E V r u n commands. Frequency reference can be set by potentiometer or FREF . • REMOTE mode: Enables run command selection (n003).
Selecting Run/Stop Commands Refer to Switching LOCAL / REMOTE Modes (page 48) to select either the LOCAL mode or REMOTE mode. Operation method (RUN / STOP commands, FWD / REV run commands) can be selected by the following method.
Operating (RUN / STOP commands) by communications Setting constant n003 to 2 in REMOTE mode can give RUN / STOP commands by communication (MEMOBUS communications). For the command by communications, refer to page 89) Selecting Frequency Reference Frequency reference can be selected by the following methods. Setting by operator Select REMOTE or LOCAL mode in advance. For the method for selecting the mode, refer to page 48. LOCAL mode Select command method by constant n008.
Example of frequency reference by voltage signal IM FS n004 = 2 (initial setting : 1) FREQUENCY SETTING POWER +12V, 20mA MASTER SPEED (0 TO +10V) FREQUENCY FR REFERENECE FC(0V) 2KΩ Setting Operation Conditions Reverse run prohibit (n006) “Reverse run prohibit” setting does not accept a reverse run command from the control circuit terminal or digital operator. This setting is used for applications where a reverse run command can cause problems. Setting Description 0 Reverse run enabled.
FREQUENCY REFERENCE (n031) 60.0 Hz (n030) 55.0 Hz (n029) 50.0 Hz (n028) 45.0 Hz (n027) 40.0 Hz (n026) 35.0 Hz (n025) 30.0 Hz (n024) 25.0 Hz TIME ON FWD (REV) RUN/STOP ON MULTI-STEP SPEED REF. 1 (TERMINAL S5) MULTI-STEP SPEED REF. 2 (TERMINAL S6) MULTI-STEP SPEED REF. 3 (TERMINAL S7) ON ON ON ON ON ON 16-Step speed operation Set frequency reference 9-16 to n120-127. Set input terminal to multi-step speed reference for multi-function input selection.
Adjusting speed setting signal To provide frequency reference by analog input of control circuit terminal FR or FC, the relationship between analog input and frequency reference can be set. FREQURNCY REFERENCE MAX. OUTPUT FREQUENCY GAIN 100 MAX. OUTPUT FREQUENCY BIAS 100 0V (4mA) (0mA) 10V (20mA) (20mA) ( ) indicates the value when current reference input is selected.
• To operate the inverter with frequency reference of 50% to 100% at 0 to 10V input MAX. FREQUENCY (100%) 50% 0V 10V Gain n060 = 100 Bias n061 = 50 Adjusting frequency upper and lower limits • Frequency reference upper limit (n033) Sets the upper limit of the frequency reference in units of 1%. (n011: Max.
Using four accel/decel times OUTPUT FREQUENCY ACCEL TIME 1 (n019) ACCEL TIME 2 (n021) FORWARD (REVERSE) RUN COMMAND MULTI-STEP SPEED REFERENCE ACCEL/DECEL TIME SELECTION(1) ACCEL/DECEL TIME SELECTION(2) ACCEL DECEL TIME 2 ACCEL TIME 4 (n022) DECEL TIME 3 (n043) TIME 1 (n041) (n020) DECEL TIME 4* (n044) DECEL TIME 3* (n042) TIME ON ON ON ON ON * When “deceleration to a stop” is selected (n005 = 0).
n018 setting No. Unit 0.1s 0 n018 1 Setting range 0.0-999.9s (999.9s or less) 1s 1000-6000s (1000s or more) 0.01s 0.00-99.99s (99.99s or less) 0.1s 100.0-600.0s (100s or more) Notes: Constant n018 can be set during stop. If the value exceeding 600.0 s is set for the accel/decel time when n018 = 0 (in units of 0.1 s), “1” cannot be set to n018. • Accel time Set the time needed for output frequency to reach 100% from 0%. • Decel time Set the time needed for output frequency to reach 0% from 100%.
Soft-start characteristics (n023) To prevent shock at machine start/stop, accel/decel can be performed in Scurve pattern. Setting 0 1 2 3 S-curve selection S-curve characteristic not provided 0.2 s 0.5 s 1.0 s Note : S-curve characteristic time is the time from accel/decel rate 0 to a regular accel/decel rate determined by the set accel/decel time.
Torque detection If an excessive load is applied to the machine, output current increase can be detected to output alarm signals to multi-function output terminals MA, MB, P1 and P2. To output an overtorque detection signal, set output terminal function selection n057 to n059 to “overtorque detection” [ Setting:6 (NO contact) or 7 (NC contact)].
• Overtorque detection function selection 1 (n096) Setting 0 1 2 3 4 Description Overtorque detection not provided Detected during constant-speed running, and operation continues after detection. Detected during constant-speed running, and operation stops during detection. Detected during running, and operation continues after detection. Detected during running, and operation stops during detection. (1) To detect overtorque at accel/decel, set to 3 or 4.
Frequency detection (n095) Effective when either of output terminal function selections n057, n058 or n059 are set to “frequency detection” (setting: 4 or 5). “Frequency detection” turns ON when output frequency is higher or lower than the setting of frequency detection (n095). • Frequency detection 1 Output frequency Frequency detection level n095 (Set either of n057, n058 or n059 to “4”.
Jump frequencies (n083 to n086) This function allows the prohibition or “jumping” of critical frequencies so that the motor can operate without resonance caused by machine systems. This function is also used for dead band control. Setting the value to 0.00Hz disables this function.
Operating coasting motor without trip To operate coasting motor without trip, use the speed search command or DC injection braking at start. • Speed search command Restarts a coasting motor without stopping it. This function enables smooth switching between motor commercial power supply operation and inverter operation. Set multi-function input selection (n050 to n056) to “14” (search command from maximum output frequency) or “15” (search command from set frequency).
Holding accel/decel temporarily To hold acceleration or deceleration, input accel/decel hold command. The output frequency is maintained when the accel/decel hold command is input during acceleration or deceleration. When the stop command is input during accel/decel prohibition command input, accel/decel hold is released and operation ramps to stop. Set multi-function input selection (n050 to n056) to 16 (accel/decel prohibit).
Using frequency meter or ammeter (n066) Selects to output either output frequency or output current to analog output terminals AM-AC for monitoring. Setting Description 0 Output frequency 1 Output current 2 Main circuit DC voltage 3 Torque monitor 4 Output power 5 Output voltage reference 6 Frequency reference monitor In initial setting, analog voltage of approx. 10V is output when output frequency (output current) is 100%.
Using analog output(AM-AC) as a pulse train signal output (n065) Analog output AM-AC can be used as a pulse train output (output frequency monitor, frequency reference monitor). Set n065 to 1 when using pulse train output. Constant No. Name n065 Monitor output type Unit Setting range Initial setting 0,1 0 1 n065 setting n065 setting Description 0 Analog monitor output 1 Pulse monitor output ( Output frequency monitor ) Pulse train signal can be selected by setting n150.
NOTE Peripheral devices must be connected according to the following load conditions when using pulse monitor output. The machine might damage when the conditions are not satisfied. Used as a sourcing output Output voltage VRL ( V ) +5V Load impedance Load impedance ( kΩ ) 1.5 kΩ or more +8V 3.
Reducing motor noise or leakage current (n080) Set inverter output transistor switching frequency (carrier frequency). Setting Carrier Frequency (kHz) Metallic Noise from Motor (Hz) 7 12 fout 8 24 fout (Hz) 9 36 fout (Hz) 1 2.5 (kHz) 2 5.0 (kHz) 3 7.5 (kHz) 4 10.0 (kHz) Noise and Current Leakage Higher Smaller Not audible Larger Setting values 7, 8, or 9 multiplies output frequency according to output frequency value. n080=7 fc=CARRIER FREQUENCY 2.5kHz fc=12 fout 1.
Factory setting varies according to inverter capacity (kVA). Voltage Class Capacity (kW) (V) 200 Single-phase 3-phase 400 3-phase NOTE 0.1 0.25 0.55 1.1 1.5 2.2 4.0 0.37 0.55 1.1 1.5 2.2 3.0 4.0 Carrier Frequency Maximum Continuous Output Current (A) 10kHz 10kHz 10kHz 10kHz 7.5kHz 7.5kHz 7.5kHz 7.5kHz 7.5kHz 7.5kHz 7.5kHz 7.5kHz 7.5kHz 7.5kHz 0.8 1.6 3.0 5.0 8.0 11.0 17.5 1.2 1.8 3.4 4.8 5.5 7.2 9.2 Initial Setting Setting 4 4 4 4 3 3 3 3 3 3 3 3 3 3 Reduced Current (A) ---7.0 10.0 16.5 1.0 1.6 3.
(3) Set carrier frequency selection (n080) to either 1, 2, 3, 4 when using vector control mode. Do not set to 7, 8, or 9. (4) Carrier frequency is automatically reduced to 2.
Selecting Stopping Method Selecting stopping method (n005) Selects the stopping method suitable for application. Setting Description 0 Deceleration to stop 1 Coast to stop • Deceleration to stop Example when accel/decel time 1 is selected ACCEL OUTPUT FREQUENCY TIME 1 (n019) DECEL TIME 1 (n020) * DECEL TIME 1 (n020) * TIME FWD (REV) RUN COMMAND ON MIN. OUTPUT FREQUENCY (FREQUENCY AT DC INJECTION BRAKING START) n16 (FACTORY SETTING: 1.
• Coast to stop Example when accel/decel time 1 is selected OUTPUT ACCEL FREQUENCY TIME 1 (n019) * DECEL TIME 1 (n020) COAST TO STOP * TIME FWD (REV) RUN COMMAND ON * When frequency reference is changed during running. Upon removal of the FWD (REV) run command, the motor starts coasting. Applying DC injection braking • DC injection braking current (n089) Sets DC injection braking current in units of 1%.
Building Interface Circuits with External Devices Using input signals Multi-function input terminal S1 to S7 functions can be changed when necessary by setting constants n050 to n056 respectively. The same value cannot be set to different constant settings.
Initial setting No. Terminal Initial Setting Function n050 n051 n052 n053 n054 n055 n056 S1 S2 S3 S4 S5 S6 S7 1 2 3 5 6 7 10 Forward run command (2-wire sequence) Reverse run command (3-wire sequence) External fault Fault reset Multi-step speed reference 1 Multi-step speed reference 2 JOG command Terminal function at 3-wire sequence selection When 0 is set at the terminal S3 (n052), terminal S1 becomes run command, terminal S2 becomes stop command, and terminal S3 becomes FWD/REV run command.
(Example) Set n003 = 1, n004 = 2, n008 = 0. Open : Run by frequency reference from multi-function input terminal FR and run command from multi-function input terminals S1 to S7. Closed : Run by potentiometer frequency reference and run command from the digital operator.
Notes : 1. When UP/DOWN command is selected, the upper limit speed is set regardless of frequency reference. Upper limit speed = Maximum output frequency (n011) Frequency reference upper limit (n033)/100 2. Lower limit value is either minimum output frequency (n016) or frequency reference lower limit (n034) (whichever is larger.). 3. When the FWD (REV) run command is input, operation starts at the lower limit speed without an UP/DOWN command. 4.
Using multi-function analog input ( n077, n078, n079 ) The input analog signal (0 to 10V or 4mA to 20mA) for the CN2 terminal of the JVOP-140 digital operator can be used as an auxiliary function for the main speed frequency reference input to the control circuit terminals (FR or RP). Refer to the block diagram on page111 for details of the input signal.
Analog input level 1 Auxiliary frequency reference (n077=1) 2 Frequency reference gain (n077=2) FREF2 FGAIN 100% 2.00 1.00 0% 0V (4mA) 0 10V (20mA) 0V (4mA) 5V 10V (20mA) 100%=Max. output frequency(n011) 4 Output voltage bias (n077=4) 3 Frequence reference bias (n077=3) VBIAS FBIAS 100% n079 0% 0V (4mA) 5V 10V (20mA) 0% -n079 0V (4mA) 10V (20mA) The VBIAS value to be added is doubled for 400V class inverters. Multi-function analog input signal selection (n078) Constant No.
Using output signals (n057, n058, n059) Multi-function output terminal MA, MB, P1 and P2 functions can be changed when necessary by setting constants n057, n058, and n059.
Initial setting of multi-function output terminal No.
Setting Frequency by Current Reference Input FOUT F/R DSPL DATA ENTER IOUT MNTR LO/RE PRGM RUN MAX MIN STOP RESET 1 OMRON G5S SW2 SW2 DIGITAL OPERATOR JVOP-140 FREF < > When setting frequency by inputting current reference (4-20mA or 0-20mA) from the control circuit terminal FR, switch the DIP switch SW1 on the control circuit board to “I” side. SW1 is accessed by removing the digital operator.
Current reference selection After changing DIP switch (V-I switch of SW2) to the “I” side, PRESS PRGM on the digital operator, then set the following constants. Current reference ( 4 to 20mA ).... constant n004 = 3 Current reference ( 0 to 20mA )....
Frequency Reference by Pulse Train Input Frequency reference can be set by pulse train input from the multi-function input terminal. • Input pulse specifications • Low-level voltage: 0.8V or less • High-level voltage: 3.5 to 32V • H duty: 30 to 70% • Pulse frequency: 0 to 33 kHz • Frequency reference method Frequency reference is a value obtained by multiplying the ratio of the maximum input pulse frequency and actual input pulse frequency by the maximum output frequency.
Preventing Motor from Stalling (Current Limit) Automatically adjusts the output frequency and output current according to the load to continue operation without stalling the motor. • Stall prevention (current limit) level during acceleration (n093) Sets the stall prevention (current limit) level during acceleration in units of 1%. (Inverter rated current = 100%) Factory setting: 170% A setting of 200% disables the stall prevention (current limit) during acceleration.
• Stall prevention (current limit) level during running (n094) Sets the stall prevention (current limit) level during running in units of 1%. (Inverter rated current = 100%) Factory setting: 160% A setting of 200% disables the stall prevention (current limit) during running. If stall prevention action current at agreed speed exceeds the value set for n094 for longer than 100msec, deceleration starts. When the output current exceeds the value set for n094, deceleration continues.
n115 Setting Setting 0 Function The stall prevention level becomes the level set for the constant n094 in all frequency areas. The following shows that the stall prevention level is automatically decreased in the constant output range (Max. frequency>Max. voltage output frequency). The lower limit is 40% of the set value of n094. Constant output area Operation level 1 Operation level = n094 x max.
Decreasing Motor Speed Fluctuation Slip compensation ( When n002 is set to 0 ) As the load becomes larger, motor speed is reduced and motor slip value is increased. The slip compensating function controls the motor speed at a constant value even if the load varies. When inverter output current is equal to the motor rated current (n036), the compensation frequency is added to the output frequency.
Motor Protection Motor overload detection The VS-606V7 protects against motor overload with a built-in electronic thermal overload relay. • Motor rated current (elctronic thermal reference current, n036) Set to the rated current value shown on the motor nameplate. Note : Setting to 0.0A disables the motor overload protective function.
• General-purpose motor and inverter motor Induction motors are classified as general-purpose motors or inverter motors, based on their cooling capabilities. Therefore, the motor overload function operates differently between these two motor types. Example of 200V class motor Cooling Effect General-purpose Motor Effective when operated at 50/60Hz from commercial power supply.
Selecting Cooling Fan Operation In order to increase lifetime, the cooling fan can be set to operate only when inverter is running. n039 = 0 (Initial setting) : Operates only when inverter is running (Continues operation for 1 minute after inverter is stopped.) = 1 : Operates with power ON Using MEMOBUS (MODBUS) Communications Serial communication is available with VS-606V7 using programmable controller (MEMOCON series) and MEMOBUS. Refer to MEMOBUS Instruction Manual (Manual No.: TOEZ-C736-70.
Communications connection terminal Use the following S+, S-, R+ and R- terminals for MEMOBUS communications. Change the termination resistor as shown below. At RS-422, RS-485 communications: Turn ON SW2 ON/OFF switch of only the inverter at the termination viewed from the PLC. S S RS-422A or RS-485 R SW2 R TERMINAL RESISTOR (1/2W, 120Ω) SW2 ON/OFF SWITCH SW2 SW1 OFF V PNP NPN 12 13 1 14 2 R 3 ON I R S S Notes: 1.
Setting constants necessary for communication Communication related constants must be set for PLC communication. Constants n151 to n157 cannot be set by communication. Always set them before performing communication. Constant Name n003 Run command selection n004 Frequency reference selection n151 MEMOBUS timeover detection Monitors transmission time between the receiving the correct data from the PLC.
Message format For communications, the master (PLC) sends a command to the slave (VS-606V7) and the slave responds to it. The configuration for sending and receiving is as shown to the right. The length of the data varies according to the contents of commands (functions). The interval between messages must be maintained at the following amount.
• Read out holding register contents [03H] Reads out the contents of the holding registers with the continuous numbers for the specified quantity. The contents of holding register is divided into the upper 8 bits and the lower 8 bits. They become the data items in response message in the order of numbers. (Example) Reads out status signal, fault contents, data link status and frequency reference from the VS-606V7 (slave 2).
• Writing to several holding registers [10H] Specified data are written into the several specified holding registers from the specified number, respectively. Written data must be arranged in a command message in the order of the holding register numbers: from upper eight bits to lower eight bits. (Example) Set forward run at frequency reference 60.0 Hz to slave 1 VS-606V7 from the PLC.
Data • Reference Data (available to read out / write in) Register No.
• Monitor Data (available only for read out) 0022H 0023H 0024H 0025H-026H 0027H 0028H 0029H 96 Status signal Fault description 0021H Data link status 0020H Description bit 0 Run command 1 : Run 0 : Stop 1 Reverse run 1 : Reverse run 0 : Forward run 2 Inverter operation ready 1 : Ready 0 : Not ready 3 Fault 1 : Fault 4 Data setting error 1 : Error 5 Multi-function output 1 (1 : MA ON 0 : MA OFF) 6 Multi-function output 2 (1 : P1 ON 0 : OFF) 7 Multi-function output 3 (1 : P2 ON 0 : OFF) 8 - F (Not us
002CH Sequence input status 002BH Inverter status 002AH Alarm description Register No.
002FH-0030H 0031H 0032H 0033H-0036H 0037H 0038H 0039H 003AH 003BH-003CH 003DH 003EH-00FFH Inverter Multi-function status output Description 1 : “ON” 1 : “ON” 1 : “ON” 0 : “OFF” 0 : “OFF” 0 : “OFF” 1: Frequency reference loss Reserved Main circuit DC voltage (1 / 1V) Torque monitor (1 / 1%; 100% / Motor rated torque ; with sign) (Not used) Output Power (1/1W : with sign) PID feedback value (100% / Input equivalent to max. output frequency; 10 / 1%; without sign) PID input value (±100% / ± Max.
VS-606V7 is 100,000; do not execute the ENTER command excessively. When a constant is changed from the digital operator, the constant data on the RAM is written to the non-volatile memory without ENTER command. Register number 0900H is used only for write-in. If this register is readout, register number error (error code: 02H) occurs. Error Codes Error Code 01H 02H 03H 21H 22H Contents Function code error • Function code from PLC is other than 03H, 08H or 10H.
Performing self-test VS-606V7 is provided with a function to perform self-diagnosis for operation check of the serial communication I/F circuit. This function is called self-test. In the self-test, connect the sending terminal with the receiving terminal in the communication section. It assures if the data received by VS-606V7 is not being changed. It also checks if the data can be received normally. Carry out the self-test in the following procedure. 1. Turn ON the VS-606V7 power supply.
Using Energy-saving Control Mode Verify that the constant n002 is set to 0 (V/f control mode) when performing energy-saving control. Setting n139 to 1 enables the energysaving control function. Energy-saving Control Selection (n139) Constant No. Name Unit Setting Range Initial Setting n139 Energy-saving control selection – 0 : Disabled 1 : Enabled 0 Normally it is not necessary to change the setting.
• Energy-saving voltage lower / upper limit (n141, n142, n159, n160) Sets the upper and lower limits of the output voltage. When the value calculated in the energy-saving control mode is larger than the upper limit (or smaller than the lower limit), the value is output as a voltage reference value. The upper limit is set to prevent over-excitation, and the lower limit is set to prevent stalls when the load is light. The voltage limit is set for machines using 6Hz/60 Hz.
Energy-saving search operation In the energy-saving control mode, the max. applicable voltage is calculated using the output power. However, a temperature change or the use of another manufacturer’s motor will change the fixed constants, and the max. applicable voltage may not be emitted. In the search operation, change the voltage slightly so that the max. applicable voltage can be obtained. • Search operation Voltage Limit (n144) Limits the range where the voltage can be controlled.
• Search operation power detection hold width (n161) When the power fluctuation is less than this value, the output voltage is held for 3 seconds. Then, the search operation mode is activated. Set the hold width in % of the power which is currently held. Constant No. Name Unit Setting Range Initial Setting n161 Search operation power detection hold width % 0 to 100 10 • Power detection filter time constant (n162) Response at load change is improved when this value is small.
Motor Code The energy-saving coefficient K2 (n140) is set to a value that corresponds with that motor code (n158). Motor Type Voltage Class 200V YASKAWA Generalpurpose Motor 400V 200V YASKAWA Inverter Motor 400V Capacity Motor Code: n158 Energy-saving coefficient K2: n140 0.1 kW 0 481.7 0.2 kW 1 356.9 0.4 kW 2 288.2 0.75 kW 3 223.7 1.5 kW 4 169.4 2.2 kW 5 156.8 3.7 kW 7 122.9 0.2 kW 21 713.8 0.4 kW 22 576.4 0.75 kW 23 447.4 1.5 kW 24 338.8 2.2 kW 25 313.6 3.
Using PID Control Mode For details of the PID control setting, refer to the block diagram of the Inverter’s internal PID control or the block diagram of the operator analog speed reference. PID Control Selection: n128 Constant No. Name Unit Setting Range Initial Setting n128 PID control selection – 0 to 8 0 PID output Characteristics Function Setting 0 Disabled. 1 Enabled: deviation is subject to differential control. 2 Enabled: feedback signal is subject to differetial control.
Notes: 1.When selecting frequency reference from the control circuit terminal FR as the target or feedback value, the V-I switch of SW2 on the control circuit board must be selected depending on the input method (current or voltage input). 2.Never use the frequency reference from the control circuit terminal FR for both the target and feedback values. The frequency reference for both the target value and the feedback value becomes the same.
• Integral (I) Limit (n134) Constant No. n134 Name Upper limit of integral values Unit Setting Range Initial Setting % 0 to 100 100 This constant prevents the calculated value of the integral control from exceeding the fixed amount.There is normally no need to change the setting. Reduce the setting if there is a risk of load damage, or of the motor going out of step by the inverter’s response when the load suddenly changes.
• PID Output Gain (n163) Constant No. n163 Name PID output gain Unit Setting Range Initial Setting Multiples 0.0 to 25.0 1.0 This constant adjusts the output gain. • PID Feedback Value Adjusting Gain (n129) Constant No. n129 Name PID feedback gain Unit Setting Range Initial Setting Multiples 0.00 to 10.00 1.00 Constant n129 is the gain that adjusts the feedback value. • PID Feedback Loss Detection (n136, n137, n138) Constant No.
n004 Pulse train Operator (4 to 20mA) Operator (0 to 10 V) External terminal (0 to 20 mA) External terminal (4 to 20 mA) External terminal (0 to 10V) n164 Adjustment gain FJOG (n032) INPUT Differential time (D) PID control selection Feedback value Differential time PID offset adjustment PID output gain MNTR(U-18) 100%/FMAX PID output value Output frequency PID primary delay time PID control selection constant compensation with reminder n128=1,2,5.
A/D converter GND A/D conversion RS232C MEMOBUS communication A/D conversion RS232C MEMOBUS communication Digital operator (JVOP-140) Converts A/D (value) into Hz Max. output frequency Converts A/D (value) into Hz Max. output frequency Inverter With compensation Primary delay time constant Compensation with reminder Primary delay time constant Bias Bias Gain Gain Max. output frequency Max.
Using Constant Copy Function Constant copy function The VS-606V7 standard digital operator JVOP-140 can store constants for one inverter. A backup power supply is not necessary since EEPROM is used. Constant copy function is possible only for the inverters with same product series, power supply specifications and control mode (V/f control or vector control). However, some constants may not be copied. It is also impossible to copy constants between VS-606V7 and VSmini J7 inverters.
Constant No. n176 Name Constant copy function selection Unit - Setting Range rdy: READY rEd: READ CPy: COPY vFy: VERIFY vA: Inverter capacity display Sno: Software No. display Initial Setting rdy • Prohibiting constant read selection (n177) Select this function to prevent accidentally overwriting the constants stored in EEPROM or in the digital operator. Reading is not possible when this constant is set to 0. The constant data stored in the digital operator are safe from accidental overwriting.
READ function Reads out the constants in batch from the inverter and stores them in EEPROM inside the digital operator. When the read-out is executed, the previously stored constants data in the EEPROM are cleared and replaced with the newly entered constants. [Example] Store the constants read out from the inverter, in the EEPROM inside the digital operator. Explanation Operator display • Enable the setting of the constants n001 to n179. • Press DSPL to light [PRGM]. 001 (Can be a different constant No.
COPY function Writes the constants stored inside the digital operator in batch to the inverter. Write-in is possible only for the inverters with same product series, power supply specifications and control mode (V/f control or vector control). Therefore, writing from 200 V class to 400 V class (or vice versa), from V/f control mode to vector control mode (or vice versa), and from VS-606V7 to VSmini J7 are not possible.
[ Example ] Write the constants from EEROM inside the degital operator to the inverter Explanation • Enable the settings for the constants n001 to n179. Operator display N001 (Can be a different constant No.) • Press ENTER to display the set 1 (Lit) (Can be a different set value.) value. • Change the set value to 4 by 4 (Blinks) pressing or v key. 4 (Lit for one second) • Press ENTER. ↓ N001 (The constant No. is displayed) • Change the constant No. to n176 N176 by pressing or v key.
VERIFY function Collates the constants stored in the digital operator with the constant in the inverter. As well as write-in, VERIFY is possible only for the inverters with same product series, power supply specifications and control mode (V/f control or vector control). When the constants stored in the digital operator correspond to those in the inverter, vFy is displayed by blinking, then End is displayed.
Operator display Explanation • Display the unmatched constant No. N01 1 (Blinks) (When n011 is unmatched) • Press ENTER. • Press ENTER. 60. 0 (Blinks) • Press v • Display the constant value in the inverter. key. 50. 0 (Blinks) • Display the constant value in the digital operator. • Press DSPL or ENTER. VFY (Blinks while executing VERIFY) ↓ END(End is displayed when the execution of VERIFY is completed). N176 (The constant No. is displayed) • Continue the execution of VERIFY.
Operator display Explanation • Enable the setting for the constans n001 to n179. • Press DSPL to light [PRGM]. • Press ENTER to display the set value. • Change the set value to 4 by Pressing or v key. • Press ENTER. N001 (Can be a different constant No.) 1 (Lit) (Can be a different constant No.) 4 (Bl inks) v 4 (Lit for one second) ↓ N001 (The constant No. is displayed) • Change the constant No. to N176 n176 by pressing or v key. DY (Lit) • Press ENTER to display the set value.
Display List Operator display Description Corrective action DY Lit: Setting for constant copy function selection enabled - ED Lit: READ selected Blinks: READ under execution - CPY Lit: Writing (COPY) selected Blinks: Writing (COPY) under execution - VFY Lit: VERIFY selected Blinks: VERIFY under execution - Lit: Inverter capacity display selected - SNO Lit: Software No.
Unit selection for Frequency Reference Setting/Display Constants and monitor display for which selection of unit function is valid Item Contents Frequency reference constants Frequency reference 1 to 8 (Constants n024 to n031) Jog frequency reference (Constant n032) Frequency reference 9 to 16 (Constants n120 to n127) Frequency reference display (FREF) Monitor display Output frequency display (FOUT) Frequency reference display (U-01) Output frequency display (U-02) • Function Outline The frequency
Constant n035 Setting 40 to 3999 Description • Set the display value at 100% of frequency reference (set value of Fmax(n011)) at 1st to 4th digit of n035. By a number of 4th digit of n035, set the position of decimal point. By 1st to 4th digit of n035, set a 3-digits figure excluding decimal point. Number of 4th digit. Position of decimal point40 to 3999 0 . 1 . 2 0. 3 (Example) To display 20.0 at 100 % of frequency reference, set n035 to “1200.
Selecting Processing for Frequency Reference Loss (n064) Use this setting to select the processing performed if the level of the frequency reference signal from the control circuit terminals suddenly drops. Constant n064 Setting Description 0 Processing for frequency reference loss disabled. 1* Processing for frequency reference loss enabled.
Input/Output Open-phase Detection Constant No. n166 n167 n168 n169 Name Setting Range Initial Setting Input Open-phase Detection Level Setting unit: 1% Setting range: 0 to 100%*1 400.0 V/100% (200 V Class) 800.0 V/100% (400 V Class) 0% Input Open-phase Detection Time Setting unit: 1 s Setting range: 0 to 255 s*2 Output Open-phase Setting unit: 1% Detection Level Setting range: 0 to 100%*1 Inverter's rated output current/100% Output Open-phase Setting unit: 0.
Undertorque Detection An alarm signal can be output to a multi-function output terminal (MA, MB, P1, or P2) when the load on the machine side suddenly becomes lighter (i.e., when an undertorque occurs). To output an undertorque detection signal, set the output terminal function selection in n057, n058, or n059 to 8 (undertorque detected, NO contact) or 9 (undertorque detected, NC contact).
Underorque detection level (n118) Sets the undertorque detection current level in units of 1%. (Inverter rated current = 100%) when detected by torque is selected, motor rated torque becomes 100%. Initial setting = 10% Undertorque detection time (n119) If the time for which the motor current is less than the undertorque detection level (n118) is longer than the undertorque detection time (n119), the undertorque detection function operates. Initial setting = 0.
Using Inverters for Elevating Machines When using the VS-606V7 for elevating machines such as elevators and cranes, make sure that the brake holds and observe the following precautions for safe operation. Brake ON/OFF Sequence • For the holding brake's ON/OFF sequence, use the following inverter output signals according to the set control mode. NOTE Do not use "Running (Set value: 1)" for the holding brake's ON/OFF interlock signal.
• Sequence Circuit Configuration and Timing Chart Examples Holding brake auxiliary relay coil +24V INVERTER VS-606V7 Fault contacts MA UP S1 DOWN S2 HIGH/LOW S6 (Forward run) MB (Reverse run) MC (Multi-step speed reference 2) SC Frequency detection 1 P1 Sequence circuit BR Energizes the brake when ON (30 VDC 1 A or less) PC For the AC sequence circuit, connect the signal between P1 and PC to the sequence circuit with a relay.
Stall Prevention During Deceleration If connecting a braking resistor to discharge regenerative energy, be sure to set the stall prevention during deceleration (n092) to 1. NOTE If the stall prevention during deceleration (n092) is set to the initial value 0 (Enabled), the motor may not stop within the specified decelerating time. The stall prevention during acceleration (n093) and the stall prevention level during running (n094) should be set to their initial values to enable these functions.
External Baseblock Signal If the external baseblock command (settings 12 and 13 of n050 to n056) is input while the motor is running, the motor will immediately coast to a stop. Do not input the external baseblock command while the motor is running unless necessary. If using the external baseblock command for an emergency stop or to run start an interlock, make sure that the holding brake operates.
7. MAINTENANCE AND INSPECTION Periodical Inspection Periodically inspect the inverter as described in the following table to prevent accidents and to ensure high performance with high-reliability. Location to Check Check For Solution Terminals, unit Connection hardware is mounting screws, properly seated and etc. securely tightened. Properly seat and tighten hardware. Heatsink Built up dust, dirt, and debris Blow with dry compressed air : 39.2 104 to 58.
Replacement of cooling fan • Inverter of W-dimension (width) 68mm (2.68 inches), 140mm (5.51inches), and 170mm (6.69 inches) 1. Removal (1) Press the right and left clicks of the fan cover to direction 1, and then pull them to direction 2 to remove the fan cover from the inverter unit. (2) Pull the wiring to direction 3 from the fan cover rear face, and remove the protective tube and connector. (3) Open the left and right sides of the fan cover to remove the cooling fan from the cover. 2.
• Inverter of W-dimension (width) 108mm (4.25 inches) 1. Removal (1) Remove the front cover and terminal cover, and then remove the cooling fan connector (CN10). (2) Press the right and left clicks of the fan cover to direction 1, and pull the fan cover to direction 2 to remove it from the inverter unit. Pull out the wiring from the cable lead-in hole at the bottom of the plastic case. COOLING FAN WIRE (3) Open the right and left sides of the fan cover to remove the cover from the cooling fan. 2.
8. FAULT DIAGNOSIS Protective and Diagnostic Function This section describes the alarm and fault displays, explanations for fault conditions and corrective actions to be taken if the VS-606V7 malfunctions. < Corrective actions for models with blank cover > 1. Input fault reset or cycle the power supply OFF and ON. 2. When a fault cannot be corrected: (1) Turn the power supply OFF and check the wiring and external circuit (sequence) .
: ON : BLINKING : OFF Alarm Display and Contents Alarm Display Inverter Digital RUN (Green) Status Operator ALARM (Red) U Blinking OH Blinking CRL Blinking Causes and Corrective Actions UV (Main circuit low voltage) Check the following : Main circuit DC voltage • Power supply voltage drops below the low-voltage • Main circuit power detection level while the inverter output is OFF. supply wiring is 200V:Main circuit DC voltage connected.
Alarm Display Inverter Digital RUN (Green) Status Operator ALARM (Red) OP? Blinking Warning Fault contacts do not change state. OL3 Blinking SE Blinking UL3 136 Explanation Causes and Corrective Actions Check the setting values. OP? (Constant setting error when the constant setting is performed through the MEMOBUS communications) OP1: Two or more values are set for multifunction input selection. (constants n050 to n056) OP2: Relationship among V / f constants is not correct.
Alarm Display Inverter Digital RUN (Green) Status Operator ALARM (Red) BB Blinking EF Blinking S P Warning Blinking or Fault contacts do not change state. FRN Explanation BB (External baseblock) Baseblock command at multi-function terminal is active, the inverter output is shut OFF (motor coasting). Temporary condition is cleared when input command is removed. Check the external circuit (sequence).
Fault Display and Contents Fault Display Inverter Digital RUN (Green) Status Operator ALARM (Red) Explanation OC (Overcurrent) Inverter output current momentarily exceeds approx. 250% of rated current. OC OV (Main circuit overvoltage) Main circuit DC voltage exceeds the overvoltage Output is detection level because shut OFF of excessive regenerative and motor energy from the motor. coasts to Detection level: a stop. 200V:Stops at main circuit DC voltage below approx.
Fault Display Inverter Digital RUN (Green) Status Operator ALARM (Red) UV2 Explanation Causes and Corrective Actions UV2 (Control power supply fault) Voltage fault of control power supply is detected. Cycle power. If the fault remains, replace the inverter. OH (Cooling fin overheat) Temperature rise because of inverter overload operation or intake air temperature rise.
Fault Display Inverter Digital RUN (Green) Status Operator ALARM (Red) Explanation PF (Main circuit voltage fault) The main circuit’s DC voltage oscillated in an irregular way when not in regenerative operation. PF Causes and Corrective Actions • Open phase of input supply • Occurrence of momentary power loss • Excessive fluctuation in input supply voltage • Unbalanced line voltage Check the following: • Main circuit power supply wiring is connected.
Fault Display Inverter Digital RUN (Green) Status Operator ALARM (Red) F00 Protective Operation Output is shut OFF and motor coasts to a stop. CPF-00 Inverter cannot communicate with the digital operator for 5 sec. or more when power is turned ON. Cycle power after checking the digital operator is securely mounted. If the fault remains, replace the digital operator or inverter. CPF-01 Transmission fault occurred for 5 sec. or more when transmission starts with the digital operator.
Fault Display Inverter Digital RUN (Green) Status Operator ALARM (Red) Explanation Communication option card self diagnostic error Protective Operation Communication option card model code error Output is Communication option card shut OFF DPRAM error and motor coasts to OPR(Operator connecting fault) a stop. CE(MEMOBUS communications fault) Cauces and Corrective Actions Option card fault Replace the option card. Cycle power. If the fault remains, replace the inverter.
Troubleshooting Trouble Cause The motor does not operate when an external operation signal is input. The operation method selection is wrong. The run command (n003) is not set to Control Circuit Terminal. Set the run command (n003) to Control Circuit Terminal. Corrective Actions A 3-wire sequence is in effect. The multi-function input method (n052) is set to 3-wire sequence,and the S2 control terminal is not closed.
Trouble The motor speed is unstable. The motor speed fluctuates when operating with a light load. Cause Corrective Actions The stall prevention level during running is too low. Because the stall prevention level during running (n094) is too low, the output current reaches the set level and the speed drops. Check if the stall prevention level during running (n094) is set to an appropriate value. The load is too heavy.
9. SPECIFICATIONS Standard Specifications (200V Class) 200V single- / 3-phase Voltage Class Model CIMR-V7*C???? 3phase Singlephase Output Characteristics Max. Applicable Motor Output kW∗ Inverter Capacity(kVA) Rated Output Current(A) Power Supply 20P2 20P4 20P7 21P5 22P2 24P0 B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B4P0 0.1 0.25 0.55 1.1 1.5 2.2 4.0 0.3 0.6 1.1 1.9 3.0 4.2 6.7 0.8 1.6 3 5 8 11 17.5 3-phase, 200 to 230V (proportional to input voltage) Max.
200V single- / 3-phase 320P1 20P2 20P4 20P7 21P5 22P2 24P0 phase Model CIMR-V7*C???? Singlephase B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B4P0 Motor Overload Electronic thermal overload relay Protection Motor coasts to a stop at approx. 250% of inverter rated Instantaneous current Overcurrent Motor coasts to a stop after 1 minute at 150% of inverter Overload rated output current Overvoltage Motor coasts to a stop if DC bus voltage exceed 410V Stops when DC bus voltage is approx. 200V or less Undervoltage (approx.
200V single- / 3-phase Voltage Class Display Other Functions 3phase Model CIMR-V7*C???? Singlephase Status Indicator LED Digital Operator (JVOP-140) Terminals Wiring Distance between Inverter and Motor Enclosure Cooling Method 20P1 20P2 20P4 20P7 21P5 22P2 24P0 B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B4P0 RUN and ALARM provided as standard LED's Available to monitor frequency reference, output frequency, output current Main circuit: screw terminals Control circuit: plug-in screw terminal 100m (328
Standard Specifications (400V Class) 400V 3-phase Voltage Class Model CIMR-V7*C???? 3phase Singlephase Power Supply Output Characteristics Max. Applicable Motor Output kW* Inverter Capacity(kVA) Rated Output Current(A) 40P4 40P7 41P5 42P2 43P0 44P0 — — — — — — — 0.37 0.55 1.1 1.5 2.2 3.0 4.0 0.9 1.4 2.6 3.7 4.2 5.5 7.0 1.2 1.8 3.4 4.8 5.5 7.2 9.2 Max. Output Voltage(V) 3-phase, 380 to 460V (proportional to input voltage) Max.
400V 3-phase 340P2 40P4 40P7 41P5 42P2 43P0 44P0 phase Model CIMR-V7*C???? Single— — — — — — — phase Motor Overload Electronic thermal overload relay Protection Motor coasts to a stop at approx. 250% of inverter rated Instantaneous current Overcurrent Motor coasts to a stop after 1 minute at 150% of inverter Overload rated output current Motor coasts to a stop if DC bus voltage exceed 820V Overvoltage Undervoltage Stops when DC bus voltage is approx.
400V 3-phase Voltage Class Display Other Functions 3phase Model CIMR-V7∗C???? Singlephase Status Indicator LED Digital Operator (JVOP-140) Terminals Wiring Distance between Inverter and Motor Enclosure Cooling Method 40P2 40P4 40P7 41P5 42P2 43P0 44P0 – – – – – – – RUN and ALARM provided as standard LED's Available to monitor frequency reference, output frequency, output current Main circuit: screw terminals Control circuit: plug-in screw terminal 100m (328ft) or less † Open chassis IP20
Standard Wiring DC REACTOR THERMAL BRAKING OVERLOAD RESISTOR (OPTIONAL) RELAY (OPTIONAL) U X SHORT-CIRCUIT BAR* MCCB R/L1 S S/L2 T T/L3 FORWARD RUN/STOP REVERSE RUN/STOP IM V/T2 W/T3 S2 EXTERNAL FAULT (NO CONTACT) S3 S4 MA S5 MB S6 JOG REFERENCE MC S7 P1 SC PULSE TRAIN INPUT RP FS 2kΩ P FR P FC MULTI-FUNCTION CONTACT OUTPUT † 250VAC 1A OR LESS 30VDC 1A OR LESS FAULT SHIELDED CONNECTION TERMINAL REFERENCE PULSE TRAIN (MAX.
Connection Example of Braking Resistor Use sequencer to break power supply side on overload relay trip contact MCCB 3-PHASE POWER SUPPLY MC (R) OVERLOAD RELAY TRIP CONTACT L1(R) (S) N/L2(S) (T) L3(T) BRAKING RESISTOR B1 B2 MOTOR U/T1 V/T2 W/T3 THRX OFF ON MC BRAKING RESISTOR UNIT OVERLOAD RELAY TRIP CONTACT MC SA THRX SA MC TRX MA MC SA TRX FAULT CONTACT * Disable stall prevention during deceleration by setting n092 to 1 when using a Braking Resistor Unit.
Terminal Description Main Circuit Type Terminal R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 B1, B2 +2, +1 +1, – Name Function (Signal Level) AC power supply input Use main circuit power input. (Use terminals R/L1 and S/L2 for single-phase inverters. Never use terminal T/L3.
Sequence input connection with NPN/PNP transistor When connecting sequence inputs(S1 to S7) with transistor, turn the rotary switch SW1 depending on the polarity(0V common: NPN side, +24V common: PNP side).
Sequence connection with PNP transistor (+24V common) VS-606V7 External power supply +24V Forward run / stop S1 Reverse run / stop S2 External fault (NO) S3 Multi- Fault reset function input Multi-step speed reference1 S4 Multi-step speed reference2 S6 JOG command S7 S5 SW1 SC NPN +24V PNP 155
1.5 (0.06) Dimensions / Heat Loss 8.5 (0.33) 1.5 (0.06) Fig. 1 8.5 (0.33) Fig.
Dimensions in mm (inches)/mass in kg (lb) / Heat Loss (W) Voltage Capacity W class (kW) 68 0.1 (2.68) 68 0.25 (2.68) 68 0.55 (2.68) 200V 68 1.1 3-phase (2.68) 108 1.5 (4.25) 108 2.2 (4.25) 140 4.0 (5.51) 68 0.1 (2.68) 68 0.25 (2.68) 68 0.55 (2.68) 200V 108 single1.1 (4.25) phase 108 1.5 (4.25) 140 2.2 (5.51) 170 4.0 (6.69) 108 0.37 (4.25) 108 0.55 (4.25) 108 1.1 (4.25) 108 400V 1.5 (4.25) 3-phase 108 2.2 (4.25) 140 3.0 (5.51) 140 4.0 (5.51) H D 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.04) 128 (5.
Recommended Peripheral Devices It is recommended that the following peripheral devices should be mounted between the AC main circuit power supply and VS-606V7 input terminals R/L1, S/L2, and T/L3. • MCCB (Molded-case circuit breaker) / fuse : Be sure to connect it for wiring protection. • Magnetic contactor: Mount a surge suppressor on the coil (refer to the table shown below.) When using a magnetic contactor to start and stop the inverter, do not exceed one start per hour.
Surge suppressors Surge Suppressors Model DCR2- Specifications Code No. Large size magnetic contactors 50A22E 250VAC 0.5µF 200Ω C002417 10A25C 250VAC 0.1µF 100Ω C002482 Coils and relays 200V Control relays to 230V MY-2,-3 (OMRON) HH-22, -23(FUJI) MM-2, -4 (OMRON) • Ground fault interrupter: Select a ground fault interrupter not affected by high frequencies. To prevent malfunctions, the current should be 200mA or more and the operating time 0.1 sec. or more.
Constants List • Addition of constants accompanied by the upgraded software version The constants marked with #1, #2, and #3 are applicable for the following upgraded software version Nos.: #1: Applicable for software version No. VSP 010015 or later #2: Applicable for software version No. VSP 010020 or later #3: Applicable for software version No. VSP 010024 • Constants that can be changed during operation The constants whose numbers are in bold can be changed during operation.
First Functions (Constants n001 to n049) Register Name No. No. for Transmission 001 0101H Password 002 0102 Control mode selection (Note 6) Setting Range Setting Unit 1 1 41 0, 1 1 0 (Note 1) (Note 6) 45 1 0 49 1 1 50 1 0 70 1 0 51 1 0 0 69 011 012 010C Max. voltage 0.1 to 255.0V 0.1V 013 010D Max. voltage output frequency (base frequency) 010E Mid. output frequency 010F Mid. output frequency voltage 0110 Min. output frequency 0111 Min.
Register No. No.
Second Functions (Constants n050 to n079) Register No. No. for Transmission 050 0132 051 0133 052 0134 053 0135 054 0136 055 0137 056 0138 057 0139 058 013A 059 013B 060 013C 061 013D 062 013E 064 #3 065 0140 0141 066 0142 067 0143 068 0144 069 0145 070 0146 071 0147 072 0148 073 0149 074 014A 075 014B 076 014C Name Setting Range Setting Unit Initial User Setting Setting Ref.
Register No. No. for Transmission 077 014D #2 078 014E #2 079 014F #2 Name Multi-function analog input function Multi-function analog input signal selection Frequency reference bias(FBIAS) value Setting Range Setting Unit Initial User Setting Setting Ref. Page 0 to 4 1 0 76 0,1 1 0 76 0 to 50% 1% 10% 76 Third Functions (Constants n080 to n119) Register Name No. No.
Register Name No. No. for Transmission 101 0165 Speed search deceleration #3 time 102 0166 Speed search operation #3 level 103 0167 Torque compensation gain Torque compensation 104 0168 time constant Setting Range Setting Unit Initial User Setting Setting Ref. Page 0.1 to 10.0s 0.1s 2.0s 62 0 to 200% 1% 150% 62 0.0 to 2.5 0.1 1.0 44 0.0 to 25.5s 0.1s 0.3s 44 (note 3) 44 (note 3) 46 (note 3) 46 (note 3) 46 0.
Fourth Functions (Constants n120 to n179) Register No. No. for Transmission 166 Name Setting Range 120 0178 Frequency reference 9 0.00 to 400.0Hz 121 0179 Frequency reference 10 0.00 to 400.0Hz 122 017A Frequency reference 11 0.00 to 400.0Hz 123 017B Frequency reference 12 0.00 to 400.0Hz 124 017C Frequency reference 13 0.00 to 400.0Hz 125 017D Frequency reference 14 0.00 to 400.0Hz 126 017E Frequency reference 15 0.00 to 400.0Hz 127 017F Frequency reference 16 0.00 to 400.
Register No. No.
Register No. No.
Notes: 1. Not initialized by constant initialization. 2. Upper limit of setting range and initial setting are doubled at 400V class. 3. Changes depending on inverter capacity. Refer to the next page. 4. Changes depending on inverter capacity. Refer to page 67. 5. Initial setting of the model with digital operator JVOP-140 (with potentiometer) is 0. Setting can be set to 1 by constant initialization. 6. When control mode selection (n002) is changed, initial setting corresponds to the control mode. No.
< 400V class 3-phase No. Name – Inverter capacity n036 Motor rated current Torque compensation n105 iron loss Unit kW A – – W – 3.4 4.0 6.1 11.0 11.7 19.3 n106 Motor rated slip Line to neutral n107 (per phase)* Hz – 2.5 2.7 2.6 2.5 3.0 3.2 3.2 Ω – 41.97 19.08 11.22 5.044 3.244 1.514 1.514 n108 Motor leakage inductance n110 Motor no-load current MH % – – 224.3 73 168.8 63 80.76 52 53.25 45 40.03 35 24.84 33 24.84 33 0.37kW 0.55kW 1.1kW 1.5kW 2.2kW 3.0kW 4.0kW 0.6 1.
NOTES 171
NOTES 172
Revision History The revision dates and numbers of the revised manuals are given on the bottom of the back cover. MANUAL NO. TOE-S606-11E © Printed in Japan August 2003 98-06 11 Revision number Date of printing Date of printing June 1998 Rev. No.
Date of printing Rev. No.
VS-606V7 Series INSTRUCTION MANUAL IRUMA BUSINESS CENTER 480, Kamifujisawa, Iruma, Saitama 358-8555, Japan Phone 81-42-962-5696 Fax 81-42-962-6138 YASKAWA ELECTRIC AMERICA, INC. 2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone 1-847-887-7000 Fax 1-847-887-7370 MOTOMAN INC. HEADQUARTERS 805 Liberty Lane West Carrollton, OH 45449, U.S.A. Phone 1-937-847-6200 Fax 1-937-847-6277 YASKAWA ELETRICO DO BRASIL COMERCIO LTD.A.