Instruction manual
113
• PID Output Gain (n163)
This parameter adjusts the output gain.
• PID Feedback Value Adjusting Gain (n129)
Parameter n129 is the gain that adjusts the feedback value.
• PID Feedback Loss Detection (n136, n137, n138)
Parameter 
No.
Name Unit
Setting 
Range
Initial 
Setting
n163 PID Output gain Multiples 0.0 to 25.0 1.0
Parameter 
No.
Name Unit
Setting 
Range
Initial 
Setting
n129
PID feedback value 
adjusting gain
Multiples 0.0 to 10.0 1.00
Parameter 
No.
Name Unit
Setting 
Range
Initial 
Setting
n136
Selection of PID
feedback loss detection
-
0: No detection of PID 
feedback loss
1: Detection of PID
feedback loss
(Operation 
continued: FbL 
alarm)
2: Detection of PID 
feedback loss
(Output shut down: 
fault)
0
n137
PID feedback loss 
detection level
%
0 to 100
100%/Max. output 
frequency
0
n138
PID feedback loss 
detection time
% 0.0 to 25.5 1.0