Instruction manual

119
Writes the parameters stored inside the digital operator in batch to the inverter. Write-in is
possible only for the inverters with the same product series, power supply specifications and
control mode (V/f control or vector control).
Therefore, writing from 200 V class to 400 V class (or visa versa), from VS-606V7 to VSmini
J7 are not possible.
Parameter Copy Function Selection (n176), Parameter Read Prohibited Selection (n177),
Fault history (n178), Inverter Software No. (n179), and hold output frequency are not written.
Following parameters are not written if the inverter capacity is different
.
[Example] Write the parameters from EEROM inside the digital operator to the inverter
Copy Function
Parameter No. Name Parameter No. Name
n011 to n017 V/f setting n108 Motor leakage inductance
n036 Motor rated current n109
Torque compensation voltage
limiter
n080 Carrier frequency n110 Motor no-load current
n105 Torque compensation iron loss n140 Energy-saving coefficient K2
n106 Motor rated slip n158 Motor code
n107 Motor resistance for one phase
Explanation Operator display
Enable the setting of the
parameters n001 to n179.
Execute write-in (COPY) by
Parameter Copy Function
Selection (n176).
Press DSPL to light [PRGM].
Press ENTER to display the set
value.
Change the set value to 4 by
pressing or key.
•Press ENTER.
Change the parameter No. to
n176 by pressing or key.
Press ENTER to display the set
value.
Change the set value to CPy by
pressing or key.
•Press ENTER.
Press DSPL or ENTER
(Can be a different parameter No.)
( Lit )
(Can be a different set value.)
(Blinks)
(Lit for one second.)
(The parameter No. is
displayed)
( Lit )
(Lit)
(Blinks while executing CPY)
(End is displayed after the
execution of CPY is completed.)
(The parameter No. is
displayed.)