Instruction manual
121
Collates the parameters stored in the digital operator with the parameters in the 
inverter.  As well as write-in, VERIFY is possible only for the inverters with same 
product series, power supply specifications and control mode (V/f control or vector 
control).
When the parameters stored in the digital operator correspond to those in the inverter, 
vFy is displayed by blinking, then End is displayed.
[Example] Collate the parameters stored in EEPROM inside the digital operator 
with the parameters in the inverter.
While an unmatched parameter No. is displayed or a parameter value is displayed, 
pressing STOP/RESET interrupts the execution of VERIFY and End is displayed. 
Pressing DSPL or ENTER returns to the parameter No.
VERIFY function
Explanation Operator display
• Enable the setting of the 
parameters n001 to n179.
• Execute VERIFY by Parameter 
Copy Function selection (n176)
• Display the unmatched 
parameter No.
• Display the parameter value in 
the inverter.
• Display the parameter value in 
the digital operator.
• Continue the execution of 
VERIFY.
• Press DSPL to light [PRGM].
• Press ENTER to display the set 
value.
• Change the set value to 4 by 
pressing or key.
•Press ENTER.
• Change the parameter No. to 
n176 by pressing or key.
• Press ENTER to display the set 
value.
• Change the set value to vFY by 
pressing or key.
•Press ENTER.
•Press ENTER.
•Press ENTER.
• Press  key.
• Press DSPL or ENTER 
(Can be a different parameter No.)
  ( Lit ) 
(Can be a different set value.)
 (Blinks)
 (Lit for one second.)
 (The parameter is 
displayed)
 (Lit)
 (Lit)
 (Blinks while executing 
VERIFY)
 (Blinks) (When n001 is 
unmatched)
 (Blinks)
 (Blinks)
 (Blinks while executing 
VERIFY
 (End is displayed after the 
execution of VERIFY is completed.)
 (The parameter No. is 
displayed.)