Instruction manual
138
Alarm Display
Inverter 
Status
Explanation
Causes and
 Corrective Actions
Digital 
Operator
RUN(Green)
ALARM(RED)
Stops 
according to 
parameter.
STP (Emergency stop)
The inverter stops according 
to parameter n005 after 
receiving the emergency stop 
fault signal.
Check the external 
circuit (sequence).
FBL (PID feedback loss 
detection)
PID feedback value drops 
below the detection level.
When PID feedback loss is 
detected, the inverter 
operates according to the 
n136 setting.
Check the mechanical 
system and correct the 
cause, or increase the 
value of n137.
Fault Display
Inverter 
Status
Explanation
Causes and
 Corrective Actions
Digital 
Operator
RUN(Green)
ALARM(RED)
Option card communications 
fault.
Communication fault has 
occurred in a mode that run 
command and frequency 
reference are set from the 
communication option card.
Check the 
communications 
devices or 
communication signals.
_
(OFF)
• Insufficient power supply 
voltage
• Control power supply fault.
• Hardware fault
Check the following:
• Power supply 
voltage
• Main circuit power 
supply wiring is 
connected
• Terminal screws are 
securely tightened
• Control sequence. 
Replace the 
inverter. 