Protective Functions
Motor Overload Protection Electronic thermal overload relay
Instantaneous Over Current
Motor coasts to a stop at approx. 250% of inverter rated 
current
Overload
Motor coasts to a stop after 1 minute at 150% of inverter 
rated output current
Over Voltage Motor coasts to a stop if DC bus voltage exceed 820V
Under Voltage Stops when DC bus voltage is approx. 400V or less
Momentary Power Loss
Following items are selectable: Not provided (stops if 
power loss is 15ms or longer), continuous operation if 
power loss is approx. 0.5s or shorter, continuous operation
Cooling Fin Overheat Protected by electronic circuit
Stall Prevention Level
Can be set to individual levels during accel/decel, 
provided/not provided available during coast to a stop
Cooling Fan Fault Protected by electronic circuit (fan lock detection)
Ground Fault Protected by electronic circuit (over current level)
Power Charge Indication ON until the DC bus voltage becomes 50V or less. 
Other 
Functions
Input Signals
Multi-function Input
Seven of the following input signals are selectable: 
Forward/reverse run (3-wire sequence), fault reset, 
external fault (NO/NC contact input), multi-step speed 
operation, Jog command, accel/decel time select, external 
baseblock (NO/NC contact input), speed search 
command, accel/decel hold command, LOCAL/REMOTE 
selection, communication/control circuit terminal selection, 
emergency stop fault emergency stop alarm, UP/DOWN 
command, self-test, PID control cancel, PID intregal reset/
hold
Output Signals
Multi-function Output
Following output signals are selectable (1 NO/NC contact 
output, 2 photo-coupler outputs): Fault, running, zero 
speed, at frequency, frequency detection (output 
frequency 
≤
 or 
≥
 set value), during over torque detection, 
during under voltage detection, minor error, during 
baseblock, operation mode, inverter run ready, during fault 
retry, during UV, during speed search, data output through 
communication, PID feedback loss detection
Standard Functions
Voltage vector control, full-range automatic torque boost, 
slip compensation, DC injection braking current/time at 
start/stop frequency reference bias/gain, MEMOBUS 
communications (RS-485/422, max. 19.2K bps), PID 
control, energy-saving control, parameter copy, frequency 
reference with built-in potentiometer, Unit selection for 
frequency reference setting/display
*
The protection functions at approximately 50% of inverter rated output 
current. 
Voltage Class 400V 3-phase
Model
CIMR-V7*C
‰‰‰‰
3-phase 40P2 40P4 40P7 41P5 42P2 43P0 43P7 45P5 47P5
Single-phase – – – ––––––