Instruction manual
160
084 0154 Jump frequency 2
0.00 to 
400.0Hz
0.01Hz (less 
than 100Hz) / 
0.1Hz (100Hz 
or more)
0.00Hz 60
085 0155 Jump frequency 3
0.00 to 
400.0Hz
0.01Hz (less 
than 100Hz) / 
0.1Hz (100Hz 
or more)
0.00Hz 60
086 0156 Jump frequency width
0.00 to 
25.50Hz
0.01Hz 0.00Hz 60
087 0157
Cumulative operation 
time selection (Note 9)
0.1 1 0 61
088 0158 Cumulative operation  0 to 6550 1=10H 0H 61
089 0159
DC injection braking 
current
0 to 100% 1% 50% 72
090 015A
DC injection braking time 
at stop
0.0 to 25.5% 0.1s
0.0s (Note 2)
72
091 015B
DC injection braking time 
at start
0.0 to 25.5% 0.1s 0.0s ---
092 015C
Stall prevention (current 
limit) during decel
0,1 1 0 88
093 015D
Stall prevention (current 
limit) during accel
30 to 200% 1% 170% 86
094 015E
Stall prevention (current 
limit) during running
30 to 200% 1% 160% 87
095 015F
Frequency detection 
level
0.00 to 
400.0Hz
0.01Hz (less 
than 100Hz) / 
0.1Hz (100Hz 
or more)
0.00Hz 59
096 0160 Overtorque detection 1 0 to 4 1 0 58
097 0161 Overtorque detection 2 0.1 1 0 58
098 0162
Overtorque detection 
level
30 to 200% 1% 160% 58
099 0163
Overtorque detection 
time
0.1 to 10.0s 0.1s 0.1s 58
100 0164
Memory selection of hold 
output frequency
0,1 1 0 77
101 0165
Speed search detection 
time (Note 9)
0.1 to 10.0s
0.1s 0.2s ---
102 0166
Speed search operation 
level (Note 9)
0 to 200% 1% 150%
---
103 0167
Torque compensation 
gain
0.0 to 2.5 0.1 1.0 42
104 0168
Time parameter at 
torque compensation
0.0 to 25.5s 0.1s 0.3s 42
105 0169
Torque compensation 
iron loss
0.0 to 6550
0.01W (less 
than 100W) / 
1W (1000W or 
more)
(Note 3) 42
106 016A Motor rated slip 0.0 to 20.0Hz 0.1Hz (Note 3) 44
No.
Register 
No. for 
Trans-
mission
Name Setting Range
Setting
Unit
Initial 
Setting
User 
Setting
Ref. 
Page