Instruction manual
168
CE Conformance - Electro-Magnetic Compatibility (EMC)  
Compliance 
In order to conform to EMC standards, exclusive-use methods are required for line 
filter application, cable shielding and inverter installation. An outline of the methods 
follows.
The line filter and the inverter must be mounted on the same metal plate. The filter 
should be mounted as close to the inverter as practical. Keep cable as short as possible. 
The metal plate should be securely grounded. The ground of the line filter and inverter 
must be bonded to the metal plate with as much area as possible.
For line power input cable, screened cable is recommended at least within the panel. 
The screen of the cable should be connected to a solid ground. For the motor cable, 
screened cable (max. 20m) must be used and the screen of the motor cable is connected 
to ground at both ends by a short connection, using as large an area as practical.
For a more detailed explanation, please refer to Making YASKAWA Inverter Products 
Confirm with EMC Directive (G-TI#99012-V7).
The following table and figures show the line filter list for EMC standards and the 
installation/wiring of inverter and line filter.
Line Filter List for EMC Conformance
Recommended Line Filters for VS-606 made by Rasmi Electronics Ltd
( 200V single phase )
Rated Voltage: AC 250V  single phase
  Ambient Temperature: 40
°
C (max.)
VS-606V7 Model
Current
(A)
Weight
(kg)
Dimension
W
×
D
×
H
CIMR-V7AUB0P1
CIMR-V7AUB0P2 RS 1010-V7 10 0.6 71 x 45 x 169
CIMR-V7AUB0P4
CIMR-V7AUB0P7 RS 1020-V7 20 1.0 111 x 50 x 169
CIMR-V7AUB1P5
CIMR-V7AUB2P2 RS 1030-V7 30 1.1 144 x 50 x 174
CIMR-V7AUB3P7 RS 1040-V7 40 1.2 174 x 50 x 174