Instruction manual
6. Programming Features
133
PID Feedback Loss Detection (n136, n137, n138)
PID Upper Limit
Sets the upper limit after PID control as a percentage of the maximum 
output frequency.
Prohibition of PID Output
Zero limit occurs when the PID output is negative.
Constant 
No.
Name Unit Setting Range Factory
Setting
n136 Selection for PID 
Feedback Loss De-
tection
- 0: No detection of 
PID feedback loss
1: Detection of PID 
feedback loss, 
operation contin-
ued: FbL alarm
2: Detection of PID 
feedback loss, 
output turned 
OFF: Fault
0
n137 PID Feedback Loss 
Detection Level
1% 0 to 100
100%/Max. output 
frequency
0
n138 PID Feedback Loss 
Detection Time
0.1 s 0.0 to 25.5 1.0