A setting range check and matching check for the written constants are 
executed after the constants are written from the Digital Operator to the 
Inverter. If a constant error is found, the written constants are discarded 
and the constants stored before writing are restored.
When a setting range error is found, the constant No. where an error 
occurs is indicated by flashing.
When an inconsistency in the settings is found,   (: a number) 
is indicated by flashing.
 VERIFY Function
This function compares the constants stored in the Digital Operator with 
the constant in the Inverter. Verification is possible only for the Invert-
ers with same product series, power supply specifications, and control 
mode (V/f control or vector control).
When the constants stored in the Digital Operator are the same as those 
in the Inverter, vFy will flash, and then End will be displayed.
When the constants are not the same, the unmatched constant No. will 
be displayed.
• Execute write-in 
(COPY) using 
the Constant 
Copy Function 
Selection (n176).
•  Change the constant No. 
to n176 by pressing the 
 or   key.
•  Press   to dis-
play the set value.
•  Change the set value to 
CPy by pressing the   or 
 key.
• Press  .
• Press   or 
.
 (Lit)
 (Lit)
(Flashes while executing the copy.)
 ↓
 (End is displayed after the 
copy has been completed.)
(The constant No. is displayed.)