Instruction manual
154
• Sequence Circuit Configuration and Timing Chart Examples
For the AC sequence cir-
cuit, connect the signal 
between P1 and PC to the 
sequence circuit with a 
relay.
Design the sequence so 
that the holding brake con-
tact is open when the 
sequence operation condi-
tions are satisfied and the 
contact between P1 and PC 
is closed (ON).
Make sure that the holding 
brake contact is closed 
when the emergency stop 
signal or Inverter fault 
contact output signal is 
ON.
• For V/f Control and Vector Control
Output 
Frequency 
n095
Frequency 
Detection 
Level 1
Releasing Width -2 Hz
Time
OFF
ON
UP
DOWN
HIGH/LOW
S1
(Forward Run)
S2
(Reverse Run)
S6
(Multi-step Speed Reference 2)
SC
Frequency
Detection1
Inverter VS-606V7
Fault Contacts
MA
MB
MC
P1
PC
Energizes the brake 
when ON.
(30 VDC 1 A or less.)
Holding Brake
Auxiliary Relay Coil
+24V
Sequence
Circuit
BR
OFF
OFF
n026
n024 (Enabled when n004=1)
n095
n095
OFF
ON
ON
ON
OPEN
CLOSE
CLOSE 
S1-SC UP
S6-SC High Speed/
 Low Speed
Output Frequency
0
Frequency
Detection 1
(n058=4)
P1-PC
Holding Brake
Operation
DC Injection Brake
Time
Input
Output