Instruction manual
164
(Flash-
ing)
Detected as 
an alarm 
only. Fault 
contact out-
put is not ac-
tivated.
OP  (Constant setting 
error when constants 
are set through MEMO-
BUS communications)
OP1: Two or more values 
are set for multi-func-
tion input selection. 
(constants n050 to 
n056)
OP2: Relationship among V/f 
constants is not cor-
rect. (constants n011, 
n013, n014, n016)
OP3: Setting value of motor 
rated current exceeds 
150% of Inverter Rated 
Current. (constant 
n036)
OP4: Upper/lower limit of fre-
quency reference is re-
versed. (constants 
n033, n034)
OP5: Relationship among 
jump frequency 1, 2 
and 3 is not correct. 
(constants n083 to 
n085)
OP9: The setting of the In-
verter capacity does 
not coincide with the 
Inverter. (Contact your 
Yaskawa representa-
tive.)
Check the setting values.
Flashing
OL3 (Overtorque detec-
tion) 
Motor current exceeded the 
preset value in constant 
n098.
Overtorque detection level 
was exceeded because of in-
creased leak current due to 
excessively long wiring.
•  Reduce the load, and 
increase the acceleration/
deceleration time.
•  Refer to the paragraph of 
Reducing Motor Noise 
or Leakage Current Using 
Carrier Frequency Selec-
tion (n080) on page 81.
•  Check the wiring 
(increase of current 
caused by rare shortcir-
cuit, etc.).
Flashing
SER (Sequence error) 
Inverter received LOCAL/RE-
MOTE command or commu-
nications/control circuit termi-
nal changing signals from the 
multi-function terminal while 
the Inverter output is ON.
Check the following:
•  NO/NC contact selection 
(constant).
• Wiring is made properly.
•  Signal is not input from 
the PLC.
Alarm Display Inverter 
Sta tus
Description Causes and 
Corrective Actions
Digital 
Operator
RUN (Green) 
ALARM (Red)